Skip to Content

Dry cooler BE-2x480FC1-B01C C

Dry cooler BE-2x480FC1-B01C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x480FC1-B01C C

Heat rejection i
748.59 kW
Air flow
174,567 m³/h
Fans
8 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 174,567 m³/h
External surface 4,374.4 m²
Inner volume 814.2 dm³
Fin materialAluminium
Net weight 3,535 kg
Fans
Quantity 8
Diameter 800 mm
Speed 900 rpm
Power 14,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 89.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2x480FC1-B01C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
748.594 kW Fluid flow 129.81 m³/h Pressure drop 70.3 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
571.964 kW Fluid flow 99.21 m³/h Pressure drop 43.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 460.35 not rated not rated not rated not rated not rated
40 748.59 458.44 not rated not rated not rated not rated
45 1028.76 743.61 456.72 not rated not rated not rated
50 1306.25 1020.94 739.25 455.33 not rated not rated
55 1582.52 1295.69 1014.10 735.66 454.42 not rated
60 1858.12 1569.25 1286.45 1008.46 733.07 454.15

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 355.14 not rated not rated not rated not rated not rated
40 571.96 353.46 not rated not rated not rated not rated
45 782.41 567.83 351.96 not rated not rated not rated
50 990.80 776.05 564.22 350.59 not rated not rated
55 1198.26 982.29 770.51 561.00 349.82 not rated
60 1405.22 1187.65 974.89 765.60 558.89 349.57

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 748.594 129.81 70.3
Low speed (Y) 571.964 99.21 43.5

Dimensions

Dimension drawing of BE-2x480FC1-B01C C
Dimension drawing
Dimensions as drawn
A 2453 mm
B 2300 mm
C 10050 mm
F 2230 mm
G 10650 mm
E1 2450 mm
E2 4800 mm
H 10300 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 10650 mm
Width 2300 mm
Height 2453 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.