Skip to Content

Dry cooler BE-2x591BC5-C04C C

Dry cooler BE-2x591BC5-C04C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x591BC5-C04C C

Heat rejection i
749.63 kW
Air flow
262,473 m³/h
Fans
10 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 262,473 m³/h
External surface 1,790.5 m²
Inner volume 282.0 dm³
Fin materialAluminium
Net weight 2,616 kg
Fans
Quantity 10
Diameter 910 mm
Speed 840 rpm
Power 28,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 68.0 dB(A)
Sound power 100.4 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2x591BC5-C04C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
749.626 kW Fluid flow 130.11 m³/h Pressure drop 112.9 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
596.268 kW Fluid flow 103.49 m³/h Pressure drop 75.2 kPa above the recommended pressure drop

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 436.69 not rated not rated not rated not rated not rated
40 749.63 437.84 not rated not rated not rated not rated
45 1056.06 749.20 438.90 not rated not rated not rated
50 1360.38 1054.17 748.92 440.00 not rated not rated
55 1663.77 1357.13 1052.68 748.95 441.17 not rated
60 1966.59 1659.11 1354.46 1051.76 749.43 442.58

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 349.82 not rated not rated not rated not rated not rated
40 596.27 350.80 not rated not rated not rated not rated
45 837.02 595.91 351.69 not rated not rated not rated
50 1075.93 835.49 595.72 352.62 not rated not rated
55 1314.02 1073.31 834.35 595.83 353.70 not rated
60 1551.61 1310.29 1071.25 833.79 596.43 354.99

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 749.626 130.11 112.9
Low speed (Y) 596.268 103.49 75.2

Dimensions

Dimension drawing of BE-2x591BC5-C04C C
Dimension drawing
Dimensions as drawn
A 2511 mm
B 2300 mm
C 6450 mm
F 2230 mm
G 7050 mm
E1 1230 mm
E2 3600 mm
H 6700 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 6450 mm
Width 2300 mm
Height 2511 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.