Skip to Content

Dry cooler BE-2x591AB1-C04C C

Dry cooler BE-2x591AB1-C04C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x591AB1-C04C C

Heat rejection i
733.36 kW
Air flow
266,459 m³/h
Fans
10 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 266,459 m³/h
External surface 2,072.4 m²
Inner volume 289.2 dm³
Fin materialAluminium
Net weight 2,643 kg
Fans
Quantity 10
Diameter 910 mm
Speed 840 rpm
Power 28,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 68.0 dB(A)
Sound power 100.2 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2x591AB1-C04C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
733.364 kW Fluid flow 127.27 m³/h Pressure drop 71.9 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
593.374 kW Fluid flow 102.98 m³/h Pressure drop 49.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 418.93 not rated not rated not rated not rated not rated
40 733.36 420.99 not rated not rated not rated not rated
45 1041.36 733.70 422.82 not rated not rated not rated
50 1347.28 1040.10 734.02 424.49 not rated not rated
55 1652.21 1344.46 1039.08 734.53 426.16 not rated
60 1956.62 1647.94 1342.15 1038.54 735.40 427.98

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 341.81 not rated not rated not rated not rated not rated
40 593.37 343.44 not rated not rated not rated not rated
45 839.06 593.50 344.92 not rated not rated not rated
50 1082.84 837.89 593.74 346.30 not rated not rated
55 1325.73 1080.37 836.99 594.17 347.73 not rated
60 1568.09 1322.05 1078.47 836.59 594.97 349.32

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 733.364 127.27 71.9
Low speed (Y) 593.374 102.98 49.3

Dimensions

Dimension drawing of BE-2x591AB1-C04C C
Dimension drawing
Dimensions as drawn
A 2511 mm
B 2300 mm
C 6450 mm
F 2230 mm
G 7050 mm
E1 1250 mm
E2 3600 mm
H 6700 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 6450 mm
Width 2300 mm
Height 2511 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.