Skip to Content

Dry cooler BE-2x591AB5-B04T C

Dry cooler BE-2x591AB5-B04T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x591AB5-B04T C

Heat rejection i
732.17 kW
Air flow
279,310 m³/h
Fans
10 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 279,310 m³/h
External surface 2,125.1 m²
Inner volume 348.8 dm³
Fin materialAluminium
Net weight 2,894 kg
Fans
Quantity 10
Diameter 910 mm
Speed 840 rpm
Power 28,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 67.0 dB(A)
Sound power 100.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2x591AB5-B04T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
732.171 kW Fluid flow 127.07 m³/h Pressure drop 53.3 kPa
Heat rejection · Low speed (Y)
600.672 kW Fluid flow 104.25 m³/h Pressure drop 37.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 417.61 not rated not rated not rated not rated not rated
40 732.17 419.56 not rated not rated not rated not rated
45 1040.40 732.26 421.25 not rated not rated not rated
50 1346.62 1038.81 732.38 422.84 not rated not rated
55 1651.86 1343.42 1037.51 732.69 424.38 not rated
60 1956.59 1647.11 1340.76 1036.73 733.35 426.02

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 345.03 not rated not rated not rated not rated not rated
40 600.67 346.56 not rated not rated not rated not rated
45 850.47 600.53 347.87 not rated not rated not rated
50 1098.42 848.86 600.43 349.09 not rated not rated
55 1345.47 1095.42 847.53 600.53 350.35 not rated
60 1592.04 1341.12 1092.90 846.63 600.99 351.71

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 732.171 127.07 53.3
Low speed (Y) 600.672 104.25 37.4

Dimensions

Dimension drawing of BE-2x591AB5-B04T C
Dimension drawing
Dimensions as drawn
A 2880 mm
B 2400 mm
C 6450 mm
F 2330 mm
G 7050 mm
E1 1250 mm
E2 3600 mm
H 6700 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 7050 mm
Width 2400 mm
Height 2880 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.