Dry cooler BE-2x591EC1-B04T C

Dry cooler BE-2x591EC1-B04T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x591EC1-B04T C

Heat rejection i
964.54 kW
Air flow
259,237 m³/h
Fans
10 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 259,237 m³/h
External surface 3,180.7 m²
Inner volume 676.0 dm³
Fin materialAluminium
Net weight 3,308 kg
Fans
Quantity 10
Diameter 910 mm
Speed 840 rpm
Power 28,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 68.0 dB(A)
Sound power 100.5 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BE-2x591EC1-B04T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
964.535 kW Fluid flow 167.30 m³/h Pressure drop 109.9 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
743.919 kW Fluid flow 129.03 m³/h Pressure drop 69.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 576.90 not rated not rated not rated not rated not rated
40 964.54 576.89 not rated not rated not rated not rated
45 1342.54 961.70 576.89 not rated not rated not rated
50 1717.29 1337.13 959.39 577.16 not rated not rated
55 2090.54 1709.39 1332.63 957.78 577.76 not rated
60 2462.94 2080.19 1702.84 1329.38 957.19 579.02

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 449.58 not rated not rated not rated not rated not rated
40 743.92 449.49 not rated not rated not rated not rated
45 1030.32 741.65 449.37 not rated not rated not rated
50 1314.04 1026.07 739.85 449.62 not rated not rated
55 1596.51 1307.90 1022.64 738.71 450.25 not rated
60 1878.30 1588.52 1302.90 1020.28 738.46 451.44

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 964.535 167.30 109.9
Low speed (Y) 743.919 129.03 69.4

Dimensions

Dimension drawing of BE-2x591EC1-B04T C
Dimension drawing
Dimensions as drawn
A 2880 mm
B 2400 mm
C 6450 mm
F 2330 mm
G 7050 mm
E1 1250 mm
E2 3600 mm
H 6700 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 7050 mm
Width 2400 mm
Height 2880 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.