Skip to Content

Dry cooler BE-2x680ED5-B01T C

Dry cooler BE-2x680ED5-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x680ED5-B01T C

Heat rejection i
962.28 kW
Air flow
237,137 m³/h
Fans
12 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 237,137 m³/h
External surface 4,041.6 m²
Inner volume 942.9 dm³
Fin materialAluminium
Net weight 4,229 kg
Fans
Quantity 12
Diameter 800 mm
Speed 900 rpm
Power 21,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 58.0 dB(A)
Sound power 91.0 dB(A)
Energy class D
Connections
Inlet 5"
Outlet 5"
Defrost
BE-2x680ED5-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
962.276 kW Fluid flow 166.89 m³/h Pressure drop 89.2 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
729.851 kW Fluid flow 126.56 m³/h Pressure drop 54.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 585.81 not rated not rated not rated not rated not rated
40 962.28 584.71 not rated not rated not rated not rated
45 1328.78 958.16 583.84 not rated not rated not rated
50 1691.98 1321.86 954.72 583.35 not rated not rated
55 2053.66 1682.34 1316.05 952.18 583.37 not rated
60 2414.50 2041.35 1674.24 1311.66 950.83 584.19

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 449.00 not rated not rated not rated not rated not rated
40 729.85 447.97 not rated not rated not rated not rated
45 1002.83 726.39 447.13 not rated not rated not rated
50 1273.20 997.16 723.55 446.62 not rated not rated
55 1542.39 1265.42 992.45 721.46 446.60 not rated
60 1810.93 1532.53 1258.94 988.94 720.38 447.24

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 962.276 166.89 89.2
Low speed (Y) 729.851 126.56 54.6

Dimensions

Dimension drawing of BE-2x680ED5-B01T C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 2400 mm
C 7650 mm
F 2330 mm
G 8250 mm
E1 1250 mm
E2 1200 mm
E3 2400 mm
H 7900 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 8250 mm
Width 2400 mm
Height 2750 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.