Skip to Content

Dry cooler BE-2x680BB5-B01T C

Dry cooler BE-2x680BB5-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x680BB5-B01T C

Heat rejection i
651.42 kW
Air flow
255,965 m³/h
Fans
12 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 255,965 m³/h
External surface 1,805.7 m²
Inner volume 298.8 dm³
Fin materialAluminium
Net weight 3,275 kg
Fans
Quantity 12
Diameter 800 mm
Speed 900 rpm
Power 21,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 58.0 dB(A)
Sound power 91.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2x680BB5-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
651.417 kW Fluid flow 113.07 m³/h Pressure drop 21.4 kPa
Heat rejection · Low speed (Y)
524.450 kW Fluid flow 91.01 m³/h Pressure drop 14.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 363.49 not rated not rated not rated not rated not rated
40 651.42 366.80 not rated not rated not rated not rated
45 931.71 652.37 369.53 not rated not rated not rated
50 1209.77 930.93 653.18 371.91 not rated not rated
55 1486.79 1207.41 930.26 654.00 374.08 not rated
60 1763.25 1482.92 1205.38 929.88 655.00 376.20

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 293.80 not rated not rated not rated not rated not rated
40 524.45 296.65 not rated not rated not rated not rated
45 747.88 525.12 298.97 not rated not rated not rated
50 969.13 746.99 525.65 300.96 not rated not rated
55 1189.47 966.88 746.24 526.23 302.75 not rated
60 1409.28 1185.95 965.02 745.79 526.99 304.53

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 651.417 113.07 21.4
Low speed (Y) 524.450 91.01 14.5

Dimensions

Dimension drawing of BE-2x680BB5-B01T C
Dimension drawing
Dimensions as drawn
A 2778 mm
B 2400 mm
C 7050 mm
F 2330 mm
G 7650 mm
E1 1150 mm
E2 1100 mm
E3 2200 mm
H 7300 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 7650 mm
Width 2400 mm
Height 2778 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.