Skip to Content

Dry cooler BE-2x680BC5-B01T C

Dry cooler BE-2x680BC5-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x680BC5-B01T C

Heat rejection i
793.16 kW
Air flow
249,226 m³/h
Fans
12 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 249,226 m³/h
External surface 2,407.6 m²
Inner volume 367.0 dm³
Fin materialAluminium
Net weight 3,467 kg
Fans
Quantity 12
Diameter 800 mm
Speed 900 rpm
Power 21,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 58.0 dB(A)
Sound power 91.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2x680BC5-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
793.164 kW Fluid flow 137.66 m³/h Pressure drop 98.2 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
625.220 kW Fluid flow 108.51 m³/h Pressure drop 64.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 467.33 not rated not rated not rated not rated not rated
40 793.16 467.81 not rated not rated not rated not rated
45 1111.60 791.52 468.26 not rated not rated not rated
50 1427.67 1108.02 790.12 468.72 not rated not rated
55 1742.60 1422.22 1104.98 789.14 469.37 not rated
60 2056.93 1735.33 1417.58 1102.71 788.79 470.35

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 371.12 not rated not rated not rated not rated not rated
40 625.22 371.44 not rated not rated not rated not rated
45 873.01 623.78 371.76 not rated not rated not rated
50 1118.69 869.95 622.55 372.11 not rated not rated
55 1363.50 1114.10 867.33 621.74 372.66 not rated
60 1607.77 1357.43 1110.28 865.47 621.47 373.55

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 793.164 137.66 98.2
Low speed (Y) 625.220 108.51 64.3

Dimensions

Dimension drawing of BE-2x680BC5-B01T C
Dimension drawing
Dimensions as drawn
A 2778 mm
B 2400 mm
C 7050 mm
F 2330 mm
G 7650 mm
E1 1150 mm
E2 1100 mm
E3 2200 mm
H 7300 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 7650 mm
Width 2400 mm
Height 2778 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.