Skip to Content

Dry cooler BE-2x480CD1-B01T C

Dry cooler BE-2x480CD1-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x480CD1-B01T C

Heat rejection i
795.85 kW
Air flow
176,799 m³/h
Fans
8 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BE — BE = V-type dry cooler.
  • C
    Fan rows (optional "Nx"): 2 — Catalogue: "Fan Row no." (number before x/X).
  • D
    Number of fans per row: 4 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 80 — Ø800 mm
  • G
    Coil tube rows (2nd dimensional letter): D — 5 tube rows
  • H
    Fin spacing: 1 — 2.1 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 01 — three-phase 400 V 50 Hz, 6-pole AC fan (in this series)
  • K
    Delivery version (optional): T — T: truck delivery version

Data

Coil
Air flow 176,799 m³/h
External surface 6,703.0 m²
Inner volume 774.4 dm³
Fin materialAluminium
Net weight 4,176 kg
Fans
Quantity 8
Diameter 800 mm
Speed 900 rpm
Power 14,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 89.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2x480CD1-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
795.853 kW Fluid flow 138.04 m³/h Pressure drop 43.2 kPa
Heat rejection · Low speed (Y)
603.942 kW Fluid flow 104.75 m³/h Pressure drop 26.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 493.11 not rated not rated not rated not rated not rated
40 795.85 490.85 not rated not rated not rated not rated
45 1088.94 789.83 488.79 not rated not rated not rated
50 1378.94 1079.57 784.52 487.12 not rated not rated
55 1667.53 1366.37 1071.35 780.13 485.98 not rated
60 1955.35 1651.82 1355.36 1064.55 776.89 485.56

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 378.00 not rated not rated not rated not rated not rated
40 603.94 376.05 not rated not rated not rated not rated
45 822.47 599.02 374.28 not rated not rated not rated
50 1038.67 814.96 594.69 372.85 not rated not rated
55 1253.84 1028.70 808.40 591.13 371.86 not rated
60 1468.45 1241.47 1020.00 802.98 588.52 371.48

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 795.853 138.04 43.2
Low speed (Y) 603.942 104.75 26.3

Dimensions

Dimension drawing of BE-2x480CD1-B01T C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 2400 mm
C 10050 mm
F 2330 mm
G 10650 mm
E1 2450 mm
E2 4800 mm
H 10300 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 10650 mm
Width 2400 mm
Height 2750 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.