Skip to Content

Dry cooler BE-991AC5-B04 C

Dry cooler BE-991AC5-B04 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-991AC5-B04 C

Heat rejection i
799.22 kW
Air flow
249,268 m³/h
Fans
9 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 249,268 m³/h
External surface 2,865.4 m²
Inner volume 408.7 dm³
Fin materialAluminium
Net weight 2,631 kg
Fans
Quantity 9
Diameter 910 mm
Speed 840 rpm
Power 25,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 67.0 dB(A)
Sound power 99.5 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BE-991AC5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
799.216 kW Fluid flow 138.72 m³/h Pressure drop 30.7 kPa
Heat rejection · Low speed (Y)
640.756 kW Fluid flow 111.20 m³/h Pressure drop 20.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 459.25 not rated not rated not rated not rated not rated
40 799.22 461.39 not rated not rated not rated not rated
45 1130.20 798.53 463.14 not rated not rated not rated
50 1458.31 1127.14 797.94 464.73 not rated not rated
55 1785.09 1453.00 1124.55 797.64 466.35 not rated
60 2111.10 1777.58 1448.46 1122.58 797.88 468.21

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 371.40 not rated not rated not rated not rated not rated
40 640.76 373.04 not rated not rated not rated not rated
45 902.05 639.97 374.40 not rated not rated not rated
50 1160.63 899.15 639.28 375.66 not rated not rated
55 1418.09 1155.95 896.77 638.93 376.98 not rated
60 1674.85 1411.58 1151.97 895.06 638.97 378.51

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 799.216 138.72 30.7
Low speed (Y) 640.756 111.20 20.6

Dimensions

Dimension drawing of BE-991AC5-B04 C
Dimension drawing
Dimensions as drawn
A 1958 mm
B 1300 mm
C 11260 mm
F 1150 mm
G 11860 mm
E1 1230 mm
E2 1200 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 11860 mm
Width 1300 mm
Height 1958 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.