Skip to Content

Dry cooler BE-2x580ED5-B01T C

Dry cooler BE-2x580ED5-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x580ED5-B01T C

Heat rejection i
797.00 kW
Air flow
197,614 m³/h
Fans
10 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 197,614 m³/h
External surface 3,368.0 m²
Inner volume 760.5 dm³
Fin materialAluminium
Net weight 3,424 kg
Fans
Quantity 10
Diameter 800 mm
Speed 900 rpm
Power 18,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 57.0 dB(A)
Sound power 90.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2x580ED5-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
796.997 kW Fluid flow 138.23 m³/h Pressure drop 59.7 kPa
Heat rejection · Low speed (Y)
604.885 kW Fluid flow 104.89 m³/h Pressure drop 36.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 482.62 not rated not rated not rated not rated not rated
40 797.00 482.00 not rated not rated not rated not rated
45 1102.80 793.87 481.60 not rated not rated not rated
50 1405.71 1097.28 791.25 481.45 not rated not rated
55 1707.28 1397.90 1092.66 789.36 481.70 not rated
60 2008.11 1697.22 1391.34 1089.19 788.41 482.57

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 370.08 not rated not rated not rated not rated not rated
40 604.89 369.54 not rated not rated not rated not rated
45 832.71 602.24 369.10 not rated not rated not rated
50 1058.24 828.17 600.03 368.89 not rated not rated
55 1282.71 1051.91 824.40 598.45 369.05 not rated
60 1506.60 1274.63 1046.64 821.60 597.68 369.75

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 796.997 138.23 59.7
Low speed (Y) 604.885 104.89 36.4

Dimensions

Dimension drawing of BE-2x580ED5-B01T C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 2400 mm
C 6450 mm
F 2330 mm
G 7050 mm
E1 1250 mm
E2 3600 mm
H 6700 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 7050 mm
Width 2400 mm
Height 2750 mm

Downloads