Skip to Content

Dry cooler BE-2x680BD5-B01C C

Dry cooler BE-2x680BD5-B01C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x680BD5-B01C C

Heat rejection i
808.10 kW
Air flow
232,566 m³/h
Fans
12 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 232,566 m³/h
External surface 2,540.1 m²
Inner volume 411.7 dm³
Fin materialAluminium
Net weight 3,258 kg
Fans
Quantity 12
Diameter 800 mm
Speed 900 rpm
Power 21,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 58.0 dB(A)
Sound power 91.0 dB(A)
Energy class D
Connections
Inlet 5"
Outlet 5"
Defrost
BE-2x680BD5-B01C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
808.098 kW Fluid flow 140.24 m³/h Pressure drop 87.7 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
624.697 kW Fluid flow 108.35 m³/h Pressure drop 55.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 479.74 not rated not rated not rated not rated not rated
40 808.10 480.28 not rated not rated not rated not rated
45 1128.46 806.54 480.84 not rated not rated not rated
50 1446.07 1124.95 805.27 481.47 not rated not rated
55 1762.57 1440.73 1122.01 804.55 482.36 not rated
60 2078.39 1755.42 1436.34 1120.06 804.56 483.71

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 374.09 not rated not rated not rated not rated not rated
40 624.70 374.41 not rated not rated not rated not rated
45 868.61 623.18 374.70 not rated not rated not rated
50 1110.33 865.50 621.98 375.14 not rated not rated
55 1351.04 1105.71 863.01 621.25 375.82 not rated
60 1591.19 1344.94 1101.96 861.29 621.20 376.88

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 808.098 140.24 87.7
Low speed (Y) 624.697 108.35 55.6

Dimensions

Dimension drawing of BE-2x680BD5-B01C C
Dimension drawing
Dimensions as drawn
A 2453 mm
B 2300 mm
C 7050 mm
F 2230 mm
G 7650 mm
E1 1150 mm
E2 1100 mm
E3 2200 mm
H 7300 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 7650 mm
Width 2300 mm
Height 2453 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.