Skip to Content

Dry cooler BE-2x691EC1-C04C C

Dry cooler BE-2x691EC1-C04C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x691EC1-C04C C

Heat rejection i
1051.01 kW
Air flow
293,441 m³/h
Fans
12 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 293,441 m³/h
External surface 3,146.0 m²
Inner volume 644.3 dm³
Fin materialAluminium
Net weight 3,656 kg
Fans
Quantity 12
Diameter 910 mm
Speed 840 rpm
Power 33,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 69.0 dB(A)
Sound power 102.0 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BE-2x691EC1-C04C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
1051.008 kW Fluid flow 182.40 m³/h Pressure drop 99.5 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
805.885 kW Fluid flow 139.76 m³/h Pressure drop 62.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 623.39 not rated not rated not rated not rated not rated
40 1051.01 624.35 not rated not rated not rated not rated
45 1467.94 1049.28 625.24 not rated not rated not rated
50 1881.54 1463.78 1048.00 626.32 not rated not rated
55 2293.44 1875.01 1460.54 1047.32 627.82 not rated
60 2704.42 2284.62 1869.81 1458.49 1047.82 629.85

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 483.26 not rated not rated not rated not rated not rated
40 805.89 483.87 not rated not rated not rated not rated
45 1119.88 804.39 484.53 not rated not rated not rated
50 1430.92 1116.47 803.33 485.36 not rated not rated
55 1740.59 1425.70 1113.89 802.95 486.47 not rated
60 2049.50 1733.62 1421.67 1112.41 803.47 488.27

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 1051.008 182.40 99.5
Low speed (Y) 805.885 139.76 62.1

Dimensions

Dimension drawing of BE-2x691EC1-C04C C
Dimension drawing
Dimensions as drawn
A 2511 mm
B 2300 mm
C 7650 mm
F 2230 mm
G 8250 mm
E1 1250 mm
E2 1200 mm
E3 2400 mm
H 7900 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 7650 mm
Width 2300 mm
Height 2511 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.