BE-2x880EB5-B01C C
983.04 kW
Defrost: None
Product code: BE-2x780EC5-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 275,253 m³/h |
|---|---|
| External surface | 3,242.2 m² |
| Inner volume | 765.8 dm³ |
| Fin material | Aluminium |
| Net weight | 4,006 kg |
| Quantity | 14 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 25,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 92.0 dB(A) |
| Energy class | D |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BE-2x780EC5-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 586.42 | not rated | not rated | not rated | not rated | not rated |
| 40 | 982.98 | 586.50 | not rated | not rated | not rated | not rated |
| 45 | 1370.00 | 980.47 | 586.63 | not rated | not rated | not rated |
| 50 | 1753.98 | 1365.05 | 978.40 | 586.97 | not rated | not rated |
| 55 | 2136.54 | 1746.70 | 1360.98 | 976.95 | 587.73 | not rated |
| 60 | 2518.27 | 2126.92 | 1740.63 | 1358.03 | 976.51 | 589.01 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 458.11 | not rated | not rated | not rated | not rated | not rated |
| 40 | 760.50 | 457.96 | not rated | not rated | not rated | not rated |
| 45 | 1055.16 | 758.13 | 457.91 | not rated | not rated | not rated |
| 50 | 1347.19 | 1050.79 | 756.27 | 458.06 | not rated | not rated |
| 55 | 1638.02 | 1340.88 | 1047.24 | 755.04 | 458.46 | not rated |
| 60 | 1928.19 | 1629.82 | 1335.73 | 1044.74 | 754.65 | 459.53 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 982.978 | 170.59 | 94.1 |
| Low speed (Y) | 760.503 | 131.89 | 59.6 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 8850 mm |
| F | 2230 mm |
| G | 9450 mm |
| E1 | 1250 mm |
| E2 | 1200 mm |
| E3 | 3600 mm |
| H | 9100 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 9450 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.