Product code: BE-2x691EC5-C04C C

Heat rejection i
985.48 kW
Air flow
299,768 m³/h
Fans
12 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 299,768 m³/h
External surface 2,664.7 m²
Inner volume 644.3 dm³
Fin materialAluminium
Net weight 3,569 kg
Fans
Quantity 12
Diameter 910 mm
Speed 840 rpm
Power 33,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 69.0 dB(A)
Sound power 102.0 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BE-2x691EC5-C04C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
985.480 kW Fluid flow 171.03 m³/h Pressure drop 88.8 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
767.163 kW Fluid flow 133.16 m³/h Pressure drop 57.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 580.02 not rated not rated not rated not rated not rated
40 985.48 581.21 not rated not rated not rated not rated
45 1381.80 984.36 582.22 not rated not rated not rated
50 1775.00 1378.59 983.52 583.34 not rated not rated
55 2166.84 1769.82 1375.92 983.18 584.72 not rated
60 2557.89 2159.69 1765.48 1374.29 983.64 586.57

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 455.87 not rated not rated not rated not rated not rated
40 767.16 456.72 not rated not rated not rated not rated
45 1070.54 766.16 457.54 not rated not rated not rated
50 1371.45 1067.87 765.39 458.50 not rated not rated
55 1671.14 1367.21 1065.92 765.30 459.77 not rated
60 1970.17 1665.37 1363.96 1064.85 765.95 461.45

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 985.480 171.03 88.8
Low speed (Y) 767.163 133.16 57.0

Dimensions

Dimension drawing of BE-2x691EC5-C04C C
Dimension drawing
Dimensions as drawn
A 2511 mm
B 2300 mm
C 7650 mm
F 2230 mm
G 8250 mm
E1 1250 mm
E2 1200 mm
E3 2400 mm
H 7900 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 7650 mm
Width 2300 mm
Height 2511 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.