BE-2x880AB1-B01C C
991.98 kW
Defrost: None
Product code: BE-t-2x591GC5-B04T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 267,098 m³/h |
|---|---|
| External surface | 2,188.7 m² |
| Inner volume | 391.7 dm³ |
| Fin material | Aluminium |
| Net weight | 2,942 kg |
| Quantity | 10 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 28,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 67.0 dB(A) |
|---|---|
| Sound power | 100.1 dB(A) |
| Energy class | D |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BE-t-2x591GC5-B04T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 589.28 | not rated | not rated | not rated | not rated | not rated |
| 40 | 989.91 | 589.52 | not rated | not rated | not rated | not rated |
| 45 | 1380.21 | 987.03 | 589.77 | not rated | not rated | not rated |
| 50 | 1766.96 | 1374.42 | 984.59 | 590.13 | not rated | not rated |
| 55 | 2152.08 | 1758.41 | 1369.51 | 982.81 | 590.88 | not rated |
| 60 | 2536.30 | 2140.84 | 1751.21 | 1365.86 | 982.06 | 592.17 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 464.30 | not rated | not rated | not rated | not rated | not rated |
| 40 | 771.88 | 464.39 | not rated | not rated | not rated | not rated |
| 45 | 1070.67 | 769.43 | 464.41 | not rated | not rated | not rated |
| 50 | 1366.51 | 1065.98 | 767.44 | 464.74 | not rated | not rated |
| 55 | 1660.98 | 1359.67 | 1062.10 | 766.10 | 465.42 | not rated |
| 60 | 1954.69 | 1652.05 | 1353.99 | 1059.30 | 765.64 | 466.59 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 989.912 | 171.66 | 103.8 |
| Low speed (Y) | 771.878 | 133.87 | 66.8 |
| A | 2910 mm |
|---|---|
| B | 2400 mm |
| C | 6450 mm |
| F | 2330 mm |
| G | 7050 mm |
| E1 | 1250 mm |
| E2 | 3600 mm |
| H | 6700 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 7050 mm |
|---|---|
| Width | 2400 mm |
| Height | 2910 mm |
Our engineers answer with a selection for your conditions.