Skip to Content

Dry cooler BE-t-2x591GC5-B04T C

Dry cooler BE-t-2x591GC5-B04T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-t-2x591GC5-B04T C

Heat rejection i
989.91 kW
Air flow
267,098 m³/h
Fans
10 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 267,098 m³/h
External surface 2,188.7 m²
Inner volume 391.7 dm³
Fin materialAluminium
Net weight 2,942 kg
Fans
Quantity 10
Diameter 910 mm
Speed 840 rpm
Power 28,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 67.0 dB(A)
Sound power 100.1 dB(A)
Energy class D
Connections
Inlet 5"
Outlet 5"
Defrost
BE-t-2x591GC5-B04T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
989.912 kW Fluid flow 171.66 m³/h Pressure drop 103.8 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
771.878 kW Fluid flow 133.87 m³/h Pressure drop 66.8 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 589.28 not rated not rated not rated not rated not rated
40 989.91 589.52 not rated not rated not rated not rated
45 1380.21 987.03 589.77 not rated not rated not rated
50 1766.96 1374.42 984.59 590.13 not rated not rated
55 2152.08 1758.41 1369.51 982.81 590.88 not rated
60 2536.30 2140.84 1751.21 1365.86 982.06 592.17

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 464.30 not rated not rated not rated not rated not rated
40 771.88 464.39 not rated not rated not rated not rated
45 1070.67 769.43 464.41 not rated not rated not rated
50 1366.51 1065.98 767.44 464.74 not rated not rated
55 1660.98 1359.67 1062.10 766.10 465.42 not rated
60 1954.69 1652.05 1353.99 1059.30 765.64 466.59

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 989.912 171.66 103.8
Low speed (Y) 771.878 133.87 66.8

Dimensions

Dimension drawing of BE-t-2x591GC5-B04T C
Dimension drawing
Dimensions as drawn
A 2910 mm
B 2400 mm
C 6450 mm
F 2330 mm
G 7050 mm
E1 1250 mm
E2 3600 mm
H 6700 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 7050 mm
Width 2400 mm
Height 2910 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.