Skip to Content

Dry cooler BE-2x791EB1-B04T C

Dry cooler BE-2x791EB1-B04T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x791EB1-B04T C

Heat rejection i
1187.08 kW
Air flow
377,947 m³/h
Fans
14 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BE — BE = V-type dry cooler.
  • C
    Fan rows (optional "Nx"): 2 — Catalogue: "Fan Row no." (number before x/X).
  • D
    Number of fans per row: 7 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 91 — Ø910 mm
  • G
    Coil tube rows (2nd dimensional letter): B — 3 tube rows
  • H
    Fin spacing: 1 — 2.1 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 04 — three-phase 400 V 50 Hz, 6-pole AC fan (in this series)
  • K
    Delivery version (optional): T — T: truck delivery version

Data

Coil
Air flow 377,947 m³/h
External surface 3,339.8 m²
Inner volume 702.7 dm³
Fin materialAluminium
Net weight 4,303 kg
Fans
Quantity 14
Diameter 910 mm
Speed 840 rpm
Power 39,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 69.0 dB(A)
Sound power 102.0 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BE-2x791EB1-B04T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
1187.077 kW Fluid flow 206.05 m³/h Pressure drop 59.1 kPa
Heat rejection · Low speed (Y)
944.228 kW Fluid flow 163.88 m³/h Pressure drop 39.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 688.27 not rated not rated not rated not rated not rated
40 1187.08 690.45 not rated not rated not rated not rated
45 1674.43 1185.93 692.21 not rated not rated not rated
50 2158.01 1670.31 1184.88 693.91 not rated not rated
55 2639.91 2151.08 1666.67 1184.33 695.78 not rated
60 3120.76 2630.12 2144.94 1664.09 1184.57 698.10

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 552.35 not rated not rated not rated not rated not rated
40 944.23 554.01 not rated not rated not rated not rated
45 1326.10 943.13 555.45 not rated not rated not rated
50 1704.56 1322.61 942.36 556.91 not rated not rated
55 2081.61 1698.80 1319.69 942.05 558.62 not rated
60 2457.76 2073.57 1694.04 1317.86 942.58 560.68

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 1187.077 206.05 59.1
Low speed (Y) 944.228 163.88 39.3

Dimensions

Dimension drawing of BE-2x791EB1-B04T C
Dimension drawing
Dimensions as drawn
A 2880 mm
B 2400 mm
C 8850 mm
F 2330 mm
G 9450 mm
E1 1250 mm
E2 1200 mm
E3 3600 mm
H 9100 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 9450 mm
Width 2400 mm
Height 2880 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.