Dry cooler BE-2x980EB5-B01T C

Dry cooler BE-2x980EB5-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x980EB5-B01T C

Heat rejection i
1187.19 kW
Air flow
378,458 m³/h
Fans
18 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 378,458 m³/h
External surface 3,637.4 m²
Inner volume 862.8 dm³
Fin materialAluminium
Net weight 5,176 kg
Fans
Quantity 18
Diameter 800 mm
Speed 900 rpm
Power 32,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 61.0 dB(A)
Sound power 94.0 dB(A)
Energy class D
Connections
Inlet 5"
Outlet 5"
Defrost
BE-2x980EB5-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
1187.187 kW Fluid flow 206.06 m³/h Pressure drop 73.3 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
942.585 kW Fluid flow 163.59 m³/h Pressure drop 48.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 696.48 not rated not rated not rated not rated not rated
40 1187.19 697.28 not rated not rated not rated not rated
45 1667.15 1184.82 697.97 not rated not rated not rated
50 2143.59 1661.84 1182.79 698.72 not rated not rated
55 2618.46 2135.47 1657.28 1181.36 699.79 not rated
60 3092.37 2607.47 2128.45 1653.80 1180.78 701.27

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 557.47 not rated not rated not rated not rated not rated
40 942.59 557.79 not rated not rated not rated not rated
45 1318.50 940.10 558.06 not rated not rated not rated
50 1691.38 1313.43 938.03 558.49 not rated not rated
55 2062.74 1683.75 1309.16 936.48 559.15 not rated
60 2433.45 2052.80 1677.34 1305.77 935.77 560.26

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 1187.187 206.06 73.3
Low speed (Y) 942.585 163.59 48.6

Dimensions

Dimension drawing of BE-2x980EB5-B01T C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 2400 mm
C 11250 mm
F 2330 mm
G 11850 mm
E1 1250 mm
E2 2400 mm
E3 3600 mm
H 11500 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 11850 mm
Width 2400 mm
Height 2750 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.