BE-2x891AC1-C04C C
1316.39 kW
Defrost: None
Product code: BE-2x880AD1-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 321,831 m³/h |
|---|---|
| External surface | 6,703.0 m² |
| Inner volume | 823.3 dm³ |
| Fin material | Aluminium |
| Net weight | 5,426 kg |
| Quantity | 16 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 28,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 60.0 dB(A) |
|---|---|
| Sound power | 93.0 dB(A) |
| Energy class | D |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BE-2x880AD1-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 802.82 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1322.47 | 801.61 | not rated | not rated | not rated | not rated |
| 45 | 1827.41 | 1316.66 | 800.51 | not rated | not rated | not rated |
| 50 | 2327.46 | 1817.42 | 1311.54 | 799.74 | not rated | not rated |
| 55 | 2825.24 | 2313.45 | 1808.67 | 1307.57 | 799.76 | not rated |
| 60 | 3321.77 | 2807.29 | 2301.20 | 1801.77 | 1305.27 | 800.72 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 617.35 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1005.46 | 616.08 | not rated | not rated | not rated | not rated |
| 45 | 1381.75 | 1000.50 | 615.03 | not rated | not rated | not rated |
| 50 | 1754.20 | 1373.50 | 996.34 | 614.41 | not rated | not rated |
| 55 | 2124.86 | 1742.80 | 1366.57 | 993.26 | 614.42 | not rated |
| 60 | 2494.56 | 2110.40 | 1733.23 | 1361.32 | 991.58 | 615.36 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 1322.468 | 229.35 | 93.1 |
| Low speed (Y) | 1005.458 | 174.40 | 57.2 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 10050 mm |
| F | 2330 mm |
| G | 10650 mm |
| E1 | 1250 mm |
| E2 | 2400 mm |
| H | 10300 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 10650 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |