Skip to Content

Dry cooler BE-2x791AC1-B04T C

Dry cooler BE-2x791AC1-B04T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x791AC1-B04T C

Heat rejection i
1308.97 kW
Air flow
374,964 m³/h
Fans
14 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 374,964 m³/h
External surface 4,692.1 m²
Inner volume 619.0 dm³
Fin materialAluminium
Net weight 4,537 kg
Fans
Quantity 14
Diameter 910 mm
Speed 840 rpm
Power 39,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 69.0 dB(A)
Sound power 102.1 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BE-2x791AC1-B04T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
1308.974 kW Fluid flow 227.16 m³/h Pressure drop 115.8 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
1030.956 kW Fluid flow 178.78 m³/h Pressure drop 75.7 kPa above the recommended pressure drop

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 774.02 not rated not rated not rated not rated not rated
40 1308.97 774.66 not rated not rated not rated not rated
45 1830.98 1305.86 775.30 not rated not rated not rated
50 2348.51 1824.21 1303.20 776.03 not rated not rated
55 2864.23 2338.51 1818.61 1301.44 777.16 not rated
60 3378.78 2850.91 2330.05 1814.39 1300.58 778.92

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 615.84 not rated not rated not rated not rated not rated
40 1030.96 616.25 not rated not rated not rated not rated
45 1435.13 1028.27 616.63 not rated not rated not rated
50 1835.59 1429.65 1026.06 617.24 not rated not rated
55 2234.34 1827.43 1425.12 1024.68 618.25 not rated
60 2632.17 2223.56 1820.65 1421.90 1024.35 619.78

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 1308.974 227.16 115.8
Low speed (Y) 1030.956 178.78 75.7

Dimensions

Dimension drawing of BE-2x791AC1-B04T C
Dimension drawing
Dimensions as drawn
A 2880 mm
B 2400 mm
C 8850 mm
F 2330 mm
G 9450 mm
E1 1250 mm
E2 1200 mm
E3 3600 mm
H 9100 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 9450 mm
Width 2400 mm
Height 2880 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.