Skip to Content

Dry cooler BE-2x991AB5-B04T C

Dry cooler BE-2x991AB5-B04T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x991AB5-B04T C

Heat rejection i
1306.80 kW
Air flow
502,758 m³/h
Fans
18 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 502,758 m³/h
External surface 3,825.2 m²
Inner volume 663.0 dm³
Fin materialAluminium
Net weight 5,140 kg
Fans
Quantity 18
Diameter 910 mm
Speed 840 rpm
Power 50,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 71.0 dB(A)
Sound power 104.0 dB(A)
Energy class E
Connections
Inlet 6"
Outlet 6"
Defrost
BE-2x991AB5-B04T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
1306.797 kW Fluid flow 226.80 m³/h Pressure drop 37.5 kPa
Heat rejection · Low speed (Y)
1072.473 kW Fluid flow 186.15 m³/h Pressure drop 26.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 739.97 not rated not rated not rated not rated not rated
40 1306.80 744.26 not rated not rated not rated not rated
45 1861.88 1307.56 747.95 not rated not rated not rated
50 2413.29 1859.55 1308.30 751.30 not rated not rated
55 2962.90 2408.00 1857.67 1309.31 754.62 not rated
60 3511.55 2954.76 2403.62 1856.59 1310.90 757.98

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 611.57 not rated not rated not rated not rated not rated
40 1072.47 614.99 not rated not rated not rated not rated
45 1522.44 1072.72 617.91 not rated not rated not rated
50 1968.97 1519.97 1072.98 620.56 not rated not rated
55 2413.82 1963.94 1517.94 1073.51 623.18 not rated
60 2857.79 2406.33 1959.74 1516.65 1074.60 626.03

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 1306.797 226.80 37.5
Low speed (Y) 1072.473 186.15 26.3

Dimensions

Dimension drawing of BE-2x991AB5-B04T C
Dimension drawing
Dimensions as drawn
A 2880 mm
B 2400 mm
C 11250 mm
F 2330 mm
G 11850 mm
E1 1250 mm
E2 2400 mm
E3 3600 mm
H 11500 mm
D IN 6"
D OUT 6"
Overall [mm]
Length 11850 mm
Width 2400 mm
Height 2880 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.