Skip to Content

Dry cooler BE-2x891EC5-C04C C

Dry cooler BE-2x891EC5-C04C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x891EC5-C04C C

Heat rejection i
1305.97 kW
Air flow
399,691 m³/h
Fans
16 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 399,691 m³/h
External surface 3,554.0 m²
Inner volume 822.6 dm³
Fin materialAluminium
Net weight 4,599 kg
Fans
Quantity 16
Diameter 910 mm
Speed 840 rpm
Power 44,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 71.0 dB(A)
Sound power 104.0 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BE-2x891EC5-C04C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
1305.974 kW Fluid flow 226.65 m³/h Pressure drop 68.1 kPa
Heat rejection · Low speed (Y)
1017.043 kW Fluid flow 176.50 m³/h Pressure drop 43.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 764.72 not rated not rated not rated not rated not rated
40 1305.97 766.78 not rated not rated not rated not rated
45 1834.70 1304.92 768.66 not rated not rated not rated
50 2359.32 1830.88 1304.18 770.53 not rated not rated
55 2882.01 2352.76 1827.65 1304.05 772.72 not rated
60 3403.62 2872.79 2347.28 1825.76 1304.94 775.46

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 601.34 not rated not rated not rated not rated not rated
40 1017.04 602.92 not rated not rated not rated not rated
45 1421.95 1016.05 604.37 not rated not rated not rated
50 1823.41 1418.67 1015.47 605.95 not rated not rated
55 2223.20 1818.01 1416.31 1015.43 607.91 not rated
60 2622.07 2215.73 1813.89 1415.09 1016.53 610.36

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 1305.974 226.65 68.1
Low speed (Y) 1017.043 176.50 43.5

Dimensions

Dimension drawing of BE-2x891EC5-C04C C
Dimension drawing
Dimensions as drawn
A 2511 mm
B 2300 mm
C 10050 mm
F 2230 mm
G 10650 mm
E1 1250 mm
E2 2400 mm
H 10300 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 10050 mm
Width 2300 mm
Height 2511 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.