BE-2x880AD5-B01C C
1181.22 kW
Defrost: None
Product code: BE-2x880EC1-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 309,054 m³/h |
|---|---|
| External surface | 4,374.4 m² |
| Inner volume | 857.3 dm³ |
| Fin material | Aluminium |
| Net weight | 4,634 kg |
| Quantity | 16 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 28,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 60.0 dB(A) |
|---|---|
| Sound power | 93.0 dB(A) |
| Energy class | D |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BE-2x880EC1-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 699.83 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1175.51 | 700.59 | not rated | not rated | not rated | not rated |
| 45 | 1638.19 | 1172.53 | 701.26 | not rated | not rated | not rated |
| 50 | 2096.57 | 1631.96 | 1170.12 | 702.17 | not rated | not rated |
| 55 | 2552.85 | 2087.11 | 1626.79 | 1168.66 | 703.55 | not rated |
| 60 | 3007.98 | 2540.30 | 2079.29 | 1623.13 | 1168.36 | 705.42 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 541.14 | not rated | not rated | not rated | not rated | not rated |
| 40 | 899.17 | 541.26 | not rated | not rated | not rated | not rated |
| 45 | 1246.50 | 896.39 | 541.58 | not rated | not rated | not rated |
| 50 | 1590.21 | 1241.04 | 894.15 | 542.11 | not rated | not rated |
| 55 | 1932.24 | 1582.21 | 1236.58 | 892.71 | 543.07 | not rated |
| 60 | 2273.33 | 1921.77 | 1575.63 | 1233.42 | 892.37 | 544.64 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 1175.509 | 203.89 | 52.9 |
| Low speed (Y) | 899.171 | 155.94 | 32.8 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 10050 mm |
| F | 2230 mm |
| G | 10650 mm |
| E1 | 1250 mm |
| E2 | 2400 mm |
| H | 10300 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 10650 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.