Skip to Content

Dry cooler BE-2x880EC1-B01C C

Dry cooler BE-2x880EC1-B01C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x880EC1-B01C C

Heat rejection i
1175.51 kW
Air flow
309,054 m³/h
Fans
16 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BE — BE = V-type dry cooler.
  • C
    Fan rows (optional "Nx"): 2 — Catalogue: "Fan Row no." (number before x/X).
  • D
    Number of fans per row: 8 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 80 — Ø800 mm
  • G
    Coil tube rows (2nd dimensional letter): C — 4 tube rows
  • H
    Fin spacing: 1 — 2.1 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 01 — three-phase 400 V 50 Hz, 6-pole AC fan (in this series)
  • K
    Delivery version (optional): C — C: container delivery version

Data

Coil
Air flow 309,054 m³/h
External surface 4,374.4 m²
Inner volume 857.3 dm³
Fin materialAluminium
Net weight 4,634 kg
Fans
Quantity 16
Diameter 800 mm
Speed 900 rpm
Power 28,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 60.0 dB(A)
Sound power 93.0 dB(A)
Energy class D
Connections
Inlet 5"
Outlet 5"
Defrost
BE-2x880EC1-B01C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
1175.509 kW Fluid flow 203.89 m³/h Pressure drop 52.9 kPa
Heat rejection · Low speed (Y)
899.171 kW Fluid flow 155.94 m³/h Pressure drop 32.8 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 699.83 not rated not rated not rated not rated not rated
40 1175.51 700.59 not rated not rated not rated not rated
45 1638.19 1172.53 701.26 not rated not rated not rated
50 2096.57 1631.96 1170.12 702.17 not rated not rated
55 2552.85 2087.11 1626.79 1168.66 703.55 not rated
60 3007.98 2540.30 2079.29 1623.13 1168.36 705.42

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 541.14 not rated not rated not rated not rated not rated
40 899.17 541.26 not rated not rated not rated not rated
45 1246.50 896.39 541.58 not rated not rated not rated
50 1590.21 1241.04 894.15 542.11 not rated not rated
55 1932.24 1582.21 1236.58 892.71 543.07 not rated
60 2273.33 1921.77 1575.63 1233.42 892.37 544.64

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 1175.509 203.89 52.9
Low speed (Y) 899.171 155.94 32.8

Dimensions

Dimension drawing of BE-2x880EC1-B01C C
Dimension drawing
Dimensions as drawn
A 2453 mm
B 2300 mm
C 10050 mm
F 2230 mm
G 10650 mm
E1 1250 mm
E2 2400 mm
H 10300 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 10650 mm
Width 2300 mm
Height 2453 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.