BE-2x880EC5-B01T C
1183.31 kW
Defrost: None
Product code: BE-2x880ED5-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 302,301 m³/h |
|---|---|
| External surface | 4,631.8 m² |
| Inner volume | 1,040.2 dm³ |
| Fin material | Aluminium |
| Net weight | 4,861 kg |
| Quantity | 16 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 28,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 60.0 dB(A) |
|---|---|
| Sound power | 93.2 dB(A) |
| Energy class | D |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BE-2x880ED5-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 707.19 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1182.36 | 708.10 | not rated | not rated | not rated | not rated |
| 45 | 1644.11 | 1179.67 | 708.99 | not rated | not rated | not rated |
| 50 | 2101.25 | 1638.17 | 1177.57 | 710.14 | not rated | not rated |
| 55 | 2556.26 | 2092.28 | 1633.45 | 1176.43 | 711.42 | not rated |
| 60 | 3010.09 | 2544.35 | 2085.05 | 1630.33 | 1176.36 | 713.59 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 543.92 | not rated | not rated | not rated | not rated | not rated |
| 40 | 899.62 | 544.16 | not rated | not rated | not rated | not rated |
| 45 | 1244.26 | 896.73 | 544.44 | not rated | not rated | not rated |
| 50 | 1585.18 | 1238.67 | 894.45 | 544.96 | not rated | not rated |
| 55 | 1924.38 | 1577.05 | 1234.14 | 892.99 | 545.93 | not rated |
| 60 | 2262.62 | 1913.78 | 1570.41 | 1230.97 | 892.65 | 547.58 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 1182.362 | 205.03 | 38.8 |
| Low speed (Y) | 899.620 | 156.01 | 23.7 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 10050 mm |
| F | 2230 mm |
| G | 10650 mm |
| E1 | 1250 mm |
| E2 | 2400 mm |
| H | 10300 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 10650 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.