BE-2x891AC5-C04C C
1218.61 kW
Defrost: None
Product code: BE-2x880ED1-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 295,398 m³/h |
|---|---|
| External surface | 5,467.9 m² |
| Inner volume | 1,040.2 dm³ |
| Fin material | Aluminium |
| Net weight | 5,007 kg |
| Quantity | 16 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 28,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 93.6 dB(A) |
| Energy class | D |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BE-2x880ED1-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 741.88 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1228.41 | 742.34 | not rated | not rated | not rated | not rated |
| 45 | 1699.85 | 1224.80 | 742.85 | not rated | not rated | not rated |
| 50 | 2166.21 | 1692.70 | 1222.05 | 743.77 | not rated | not rated |
| 55 | 2630.20 | 2155.71 | 1686.99 | 1220.40 | 745.27 | not rated |
| 60 | 3092.89 | 2616.46 | 2147.26 | 1683.17 | 1220.31 | 747.71 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 565.22 | not rated | not rated | not rated | not rated | not rated |
| 40 | 925.05 | 565.07 | not rated | not rated | not rated | not rated |
| 45 | 1272.86 | 921.48 | 565.02 | not rated | not rated | not rated |
| 50 | 1616.70 | 1266.39 | 918.62 | 565.30 | not rated | not rated |
| 55 | 1958.70 | 1607.50 | 1261.13 | 916.75 | 566.14 | not rated |
| 60 | 2299.69 | 1946.85 | 1599.99 | 1257.44 | 916.18 | 567.78 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 1228.413 | 213.02 | 41.5 |
| Low speed (Y) | 925.051 | 160.45 | 24.9 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 10050 mm |
| F | 2230 mm |
| G | 10650 mm |
| E1 | 1250 mm |
| E2 | 2400 mm |
| H | 10300 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 10650 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.