Skip to Content

Dry cooler BE-2x891EC1-B04T C

Dry cooler BE-2x891EC1-B04T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x891EC1-B04T C

Heat rejection i
1526.99 kW
Air flow
414,779 m³/h
Fans
16 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BE — BE = V-type dry cooler.
  • C
    Fan rows (optional "Nx"): 2 — Catalogue: "Fan Row no." (number before x/X).
  • D
    Number of fans per row: 8 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 91 — Ø910 mm
  • G
    Coil tube rows (2nd dimensional letter): C — 4 tube rows
  • H
    Fin spacing: 1 — 2.1 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 04 — three-phase 400 V 50 Hz, 6-pole AC fan (in this series)
  • K
    Delivery version (optional): T — T: truck delivery version

Data

Coil
Air flow 414,779 m³/h
External surface 5,089.2 m²
Inner volume 1,057.3 dm³
Fin materialAluminium
Net weight 5,282 kg
Fans
Quantity 16
Diameter 910 mm
Speed 840 rpm
Power 44,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 70.0 dB(A)
Sound power 103.5 dB(A)
Energy class E
Connections
Inlet 6"
Outlet 6"
Defrost
BE-2x891EC1-B04T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
1526.994 kW Fluid flow 265.00 m³/h Pressure drop 60.8 kPa
Heat rejection · Low speed (Y)
1178.709 kW Fluid flow 204.44 m³/h Pressure drop 38.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 904.95 not rated not rated not rated not rated not rated
40 1526.99 906.02 not rated not rated not rated not rated
45 2132.55 1523.22 907.00 not rated not rated not rated
50 2732.75 2124.70 1520.29 908.26 not rated not rated
55 3330.39 2720.83 2118.19 1518.45 909.96 not rated
60 3926.60 3314.49 2710.89 2113.57 1518.01 912.53

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 706.02 not rated not rated not rated not rated not rated
40 1178.71 706.78 not rated not rated not rated not rated
45 1637.82 1175.76 707.54 not rated not rated not rated
50 2092.33 1631.61 1173.47 708.40 not rated not rated
55 2544.70 2083.02 1626.63 1172.16 709.90 not rated
60 2995.87 2532.37 2075.47 1623.27 1172.17 712.23

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 1526.994 265.00 60.8
Low speed (Y) 1178.709 204.44 38.3

Dimensions

Dimension drawing of BE-2x891EC1-B04T C
Dimension drawing
Dimensions as drawn
A 2880 mm
B 2400 mm
C 10050 mm
F 2330 mm
G 10650 mm
E1 1250 mm
E2 2400 mm
H 10300 mm
D IN 6"
D OUT 6"
Overall [mm]
Length 10650 mm
Width 2400 mm
Height 2880 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.