BE-2x891AC1-B04T C
1442.81 kW
Defrost: None
Product code: BE-2x980AD1-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 362,060 m³/h |
|---|---|
| External surface | 7,540.9 m² |
| Inner volume | 969.4 dm³ |
| Fin material | Aluminium |
| Net weight | 6,051 kg |
| Quantity | 18 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 32,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 94.0 dB(A) |
| Energy class | D |
| Inlet | 6" |
|---|---|
| Outlet | 6" |
| BE-2x980AD1-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 853.56 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1446.23 | 856.03 | not rated | not rated | not rated | not rated |
| 45 | 2018.16 | 1442.41 | 857.94 | not rated | not rated | not rated |
| 50 | 2583.11 | 2009.16 | 1438.97 | 859.77 | not rated | not rated |
| 55 | 3144.79 | 2569.28 | 2001.25 | 1436.52 | 861.97 | not rated |
| 60 | 3704.65 | 3126.32 | 2557.18 | 1995.11 | 1435.54 | 864.92 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 658.06 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1102.74 | 659.77 | not rated | not rated | not rated | not rated |
| 45 | 1529.66 | 1099.19 | 661.16 | not rated | not rated | not rated |
| 50 | 1950.79 | 1521.98 | 1096.22 | 662.62 | not rated | not rated |
| 55 | 2369.23 | 1939.33 | 1515.55 | 1094.20 | 664.38 | not rated |
| 60 | 2786.18 | 2354.14 | 1929.71 | 1510.83 | 1093.49 | 666.83 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 1446.234 | 250.82 | 21.8 |
| Low speed (Y) | 1102.737 | 191.27 | 13.3 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 11250 mm |
| F | 2330 mm |
| G | 11850 mm |
| E1 | 1250 mm |
| E2 | 2400 mm |
| E3 | 3600 mm |
| H | 11500 mm |
| D IN | 6" |
| D OUT | 6" |
| Length | 11850 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.