BE-2x991EB1-C04C C
1412.32 kW
Defrost: None
Product code: BE-2x980EC1-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 361,906 m³/h |
|---|---|
| External surface | 5,725.3 m² |
| Inner volume | 1,103.0 dm³ |
| Fin material | Aluminium |
| Net weight | 5,778 kg |
| Quantity | 18 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 32,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 94.0 dB(A) |
| Energy class | D |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BE-2x980EC1-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 850.92 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1417.13 | 850.60 | not rated | not rated | not rated | not rated |
| 45 | 1968.07 | 1412.21 | 850.35 | not rated | not rated | not rated |
| 50 | 2513.75 | 1958.81 | 1407.86 | 850.08 | not rated | not rated |
| 55 | 3056.99 | 2500.37 | 1950.78 | 1404.52 | 850.69 | not rated |
| 60 | 3598.88 | 3039.59 | 2488.78 | 1944.44 | 1402.75 | 852.22 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 657.10 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1083.16 | 656.58 | not rated | not rated | not rated | not rated |
| 45 | 1496.49 | 1078.79 | 656.15 | not rated | not rated | not rated |
| 50 | 1905.59 | 1488.72 | 1075.15 | 656.11 | not rated | not rated |
| 55 | 2312.73 | 1894.56 | 1482.22 | 1072.59 | 656.60 | not rated |
| 60 | 2718.78 | 2298.53 | 1885.33 | 1477.37 | 1071.35 | 657.93 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 1417.131 | 245.74 | 65.3 |
| Low speed (Y) | 1083.158 | 187.84 | 40.3 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 11250 mm |
| F | 2330 mm |
| G | 11850 mm |
| E1 | 1250 mm |
| E2 | 2400 mm |
| E3 | 3600 mm |
| H | 11500 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 11850 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.