BE-2x891AC5-B04T C
1338.27 kW
Defrost: None
Product code: BE-2x980ED5-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 340,089 m³/h |
|---|---|
| External surface | 5,210.7 m² |
| Inner volume | 1,154.6 dm³ |
| Fin material | Aluminium |
| Net weight | 5,402 kg |
| Quantity | 18 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 32,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 94.2 dB(A) |
| Energy class | D |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BE-2x980ED5-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 803.69 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1337.21 | 804.15 | not rated | not rated | not rated | not rated |
| 45 | 1856.09 | 1333.70 | 804.65 | not rated | not rated | not rated |
| 50 | 2370.03 | 1849.06 | 1330.98 | 805.35 | not rated | not rated |
| 55 | 2881.69 | 2359.64 | 1843.43 | 1329.39 | 806.68 | not rated |
| 60 | 3392.06 | 2868.00 | 2351.24 | 1839.67 | 1329.05 | 808.80 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 617.59 | not rated | not rated | not rated | not rated | not rated |
| 40 | 1016.88 | 617.44 | not rated | not rated | not rated | not rated |
| 45 | 1404.11 | 1013.31 | 617.36 | not rated | not rated | not rated |
| 50 | 1787.35 | 1397.57 | 1010.48 | 617.67 | not rated | not rated |
| 55 | 2168.73 | 1777.98 | 1392.24 | 1008.61 | 618.50 | not rated |
| 60 | 2549.11 | 2156.62 | 1770.31 | 1388.50 | 1008.04 | 620.13 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 1337.205 | 231.94 | 53.1 |
| Low speed (Y) | 1016.884 | 176.34 | 32.4 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 11250 mm |
| F | 2230 mm |
| G | 11850 mm |
| E1 | 1250 mm |
| E2 | 2400 mm |
| E3 | 3600 mm |
| H | 11500 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 11850 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.