BE-t-2x280GB1-B01T C
296.93 kW
Defrost: None
Product code: BE-380CD5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 67,067 m³/h |
|---|---|
| External surface | 2,387.8 m² |
| Inner volume | 317.5 dm³ |
| Fin material | Aluminium |
| Net weight | 1,520 kg |
| Quantity | 3 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 5,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | D |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BE-380CD5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 184.77 | not rated | not rated | not rated | not rated | not rated |
| 40 | 296.93 | 183.71 | not rated | not rated | not rated | not rated |
| 45 | 406.03 | 294.60 | 182.76 | not rated | not rated | not rated |
| 50 | 514.14 | 402.52 | 292.55 | 181.97 | not rated | not rated |
| 55 | 621.82 | 509.50 | 399.44 | 290.84 | 181.40 | not rated |
| 60 | 729.24 | 616.04 | 505.42 | 396.88 | 289.56 | 181.13 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 142.44 | not rated | not rated | not rated | not rated | not rated |
| 40 | 226.76 | 141.53 | not rated | not rated | not rated | not rated |
| 45 | 308.73 | 224.84 | 140.72 | not rated | not rated | not rated |
| 50 | 389.95 | 305.88 | 223.15 | 140.05 | not rated | not rated |
| 55 | 470.85 | 386.21 | 303.39 | 221.76 | 139.58 | not rated |
| 60 | 551.56 | 466.22 | 382.94 | 301.32 | 220.71 | 139.33 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 296.930 | 51.50 | 89.2 |
| Low speed (Y) | 226.760 | 39.33 | 55.3 |
| A | 1808 mm |
|---|---|
| B | 1210 mm |
| C | 7660 mm |
| F | 1050 mm |
| G | 8260 mm |
| E1 | 2430 mm |
| E2 | 2400 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 8260 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.