BE-380CD5-B01 C
296.93 kW
Defrost: None
Product code: BE-t-2x280GB1-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 82,764 m³/h |
|---|---|
| External surface | 710.5 m² |
| Inner volume | 109.3 dm³ |
| Fin material | Aluminium |
| Net weight | 1,263 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 7,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | D |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BE-t-2x280GB1-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 173.74 | not rated | not rated | not rated | not rated | not rated |
| 40 | 296.93 | 174.17 | not rated | not rated | not rated | not rated |
| 45 | 416.62 | 296.28 | 174.54 | not rated | not rated | not rated |
| 50 | 535.20 | 415.04 | 295.71 | 174.89 | not rated | not rated |
| 55 | 653.24 | 532.71 | 413.68 | 295.32 | 175.30 | not rated |
| 60 | 770.97 | 649.88 | 530.58 | 412.64 | 295.19 | 175.85 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 137.11 | not rated | not rated | not rated | not rated | not rated |
| 40 | 231.93 | 137.42 | not rated | not rated | not rated | not rated |
| 45 | 323.77 | 231.33 | 137.67 | not rated | not rated | not rated |
| 50 | 414.62 | 322.40 | 230.83 | 137.93 | not rated | not rated |
| 55 | 504.99 | 412.52 | 321.25 | 230.48 | 138.23 | not rated |
| 60 | 595.11 | 502.20 | 410.76 | 320.39 | 230.37 | 138.67 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 296.925 | 51.53 | 60.2 |
| Low speed (Y) | 231.927 | 40.22 | 38.7 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 2650 mm |
| F | 2330 mm |
| G | 3250 mm |
| E1 | 1150 mm |
| H | 2900 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 3250 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.