Skip to Content

Dry cooler BE-480BD1-B01 C

Dry cooler BE-480BD1-B01 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-480BD1-B01 C

Heat rejection i
318.35 kW
Air flow
81,363 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 81,363 m³/h
External surface 1,292.6 m²
Inner volume 150.8 dm³
Fin materialAluminium
Net weight 1,151 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.0 dB(A)
Energy class D
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BE-480BD1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
318.353 kW Fluid flow 55.21 m³/h Pressure drop 79.0 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
243.312 kW Fluid flow 42.20 m³/h Pressure drop 49.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 191.69 not rated not rated not rated not rated not rated
40 318.35 191.55 not rated not rated not rated not rated
45 441.57 317.12 191.42 not rated not rated not rated
50 563.63 439.33 316.05 191.32 not rated not rated
55 685.15 560.44 437.42 315.25 191.41 not rated
60 806.37 681.03 557.72 435.95 314.79 191.72

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 147.83 not rated not rated not rated not rated not rated
40 243.31 147.71 not rated not rated not rated not rated
45 335.91 242.29 147.59 not rated not rated not rated
50 427.58 334.13 241.44 147.56 not rated not rated
55 518.81 425.06 332.63 240.83 147.64 not rated
60 609.81 515.58 422.94 331.50 240.51 147.92

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 318.353 55.21 79.0
Low speed (Y) 243.312 42.20 49.0

Dimensions

Dimension drawing of BE-480BD1-B01 C
Dimension drawing
Dimensions as drawn
A 1808 mm
B 1210 mm
C 4860 mm
F 1050 mm
G 5460 mm
E1 1130 mm
E2 1100 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 5460 mm
Width 1210 mm
Height 1808 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.