Skip to Content

Dry cooler BE-491CC5-B04 C

Dry cooler BE-491CC5-B04 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-491CC5-B04 C

Heat rejection i
463.22 kW
Air flow
119,548 m³/h
Fans
4 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BE — BE = V-type dry cooler.
  • D
    Number of fans per row: 4 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 91 — Ø910 mm
  • G
    Coil tube rows (2nd dimensional letter): C — 4 tube rows
  • H
    Fin spacing: 5 — 2.5 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 04 — three-phase 400 V 50 Hz, 6-pole AC fan (in this series)

Data

Coil
Air flow 119,548 m³/h
External surface 2,547.0 m²
Inner volume 345.8 dm³
Fin materialAluminium
Net weight 1,840 kg
Fans
Quantity 4
Diameter 910 mm
Speed 840 rpm
Power 11,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 63.0 dB(A)
Sound power 96.0 dB(A)
Energy class D
Connections
Inlet 3"
Outlet 3"
Defrost
BE-491CC5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
463.217 kW Fluid flow 80.33 m³/h Pressure drop 60.5 kPa
Heat rejection · Low speed (Y)
366.011 kW Fluid flow 63.48 m³/h Pressure drop 39.7 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 278.98 not rated not rated not rated not rated not rated
40 463.22 278.39 not rated not rated not rated not rated
45 642.60 460.82 277.82 not rated not rated not rated
50 820.35 638.57 458.72 277.38 not rated not rated
55 997.34 814.73 635.02 456.97 277.05 not rated
60 1173.92 990.17 809.79 632.07 455.71 277.10

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 222.34 not rated not rated not rated not rated not rated
40 366.01 221.71 not rated not rated not rated not rated
45 505.55 363.85 221.12 not rated not rated not rated
50 643.74 502.01 361.93 220.64 not rated not rated
55 781.30 638.86 498.89 360.35 220.36 not rated
60 918.52 775.12 634.58 496.31 359.22 220.33

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 463.217 80.33 60.5
Low speed (Y) 366.011 63.48 39.7

Dimensions

Dimension drawing of BE-491CC5-B04 C
Dimension drawing
Dimensions as drawn
A 1958 mm
B 1210 mm
C 10060 mm
F 1050 mm
G 10660 mm
E1 2430 mm
E2 2400 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 10660 mm
Width 1210 mm
Height 1958 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.