BE-491CC5-B04 C
463.22 kW
Defrost: None
Product code: BE-t-2x380GC1-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 114,204 m³/h |
|---|---|
| External surface | 1,199.3 m² |
| Inner volume | 162.5 dm³ |
| Fin material | Aluminium |
| Net weight | 1,627 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.1 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BE-t-2x380GC1-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 277.16 | not rated | not rated | not rated | not rated | not rated |
| 40 | 463.07 | 277.47 | not rated | not rated | not rated | not rated |
| 45 | 643.19 | 461.85 | 277.81 | not rated | not rated | not rated |
| 50 | 821.34 | 640.58 | 460.83 | 278.17 | not rated | not rated |
| 55 | 998.57 | 817.42 | 638.38 | 460.11 | 278.71 | not rated |
| 60 | 1175.28 | 993.38 | 814.11 | 636.70 | 459.91 | 279.59 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 212.79 | not rated | not rated | not rated | not rated | not rated |
| 40 | 351.31 | 212.90 | not rated | not rated | not rated | not rated |
| 45 | 484.99 | 350.04 | 213.01 | not rated | not rated | not rated |
| 50 | 617.07 | 482.56 | 349.02 | 213.21 | not rated | not rated |
| 55 | 748.41 | 613.56 | 480.57 | 348.33 | 213.60 | not rated |
| 60 | 879.35 | 743.86 | 610.67 | 479.15 | 348.11 | 214.26 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 463.066 | 80.31 | 70.6 |
| Low speed (Y) | 351.314 | 60.93 | 43.1 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 3750 mm |
| F | 2230 mm |
| G | 4350 mm |
| E1 | 1150 mm |
| E2 | 1100 mm |
| H | 4000 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 4350 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.