BE-t-2x380HB5-B01T C
495.56 kW
Defrost: None
Product code: BE-491FC1-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 117,818 m³/h |
|---|---|
| External surface | 2,859.4 m² |
| Inner volume | 522.5 dm³ |
| Fin material | Aluminium |
| Net weight | 2,005 kg |
| Quantity | 4 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 11,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 96.0 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BE-491FC1-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 300.42 | not rated | not rated | not rated | not rated | not rated |
| 40 | 495.84 | 299.81 | not rated | not rated | not rated | not rated |
| 45 | 685.10 | 493.00 | 299.21 | not rated | not rated | not rated |
| 50 | 872.29 | 680.25 | 490.46 | 298.75 | not rated | not rated |
| 55 | 1058.52 | 865.54 | 675.99 | 488.39 | 298.52 | not rated |
| 60 | 1244.22 | 1049.91 | 859.62 | 672.49 | 486.93 | 298.65 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 235.38 | not rated | not rated | not rated | not rated | not rated |
| 40 | 384.91 | 234.77 | not rated | not rated | not rated | not rated |
| 45 | 529.35 | 382.45 | 234.19 | not rated | not rated | not rated |
| 50 | 672.13 | 525.29 | 380.28 | 233.73 | not rated | not rated |
| 55 | 814.14 | 666.54 | 521.73 | 378.50 | 233.48 | not rated |
| 60 | 955.74 | 807.08 | 661.67 | 518.81 | 377.25 | 233.54 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 495.838 | 85.98 | 30.1 |
| Low speed (Y) | 384.910 | 66.76 | 19.0 |
| A | 1958 mm |
|---|---|
| B | 1210 mm |
| C | 10060 mm |
| F | 1050 mm |
| G | 10660 mm |
| E1 | 2430 mm |
| E2 | 2400 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 10660 mm |
|---|---|
| Width | 1210 mm |
| Height | 1958 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.