BE-t-580GC1-B01 C
433.12 kW
Defrost: None
Product code: BE-580ED1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 100,131 m³/h |
|---|---|
| External surface | 2,233.9 m² |
| Inner volume | 415.7 dm³ |
| Fin material | Aluminium |
| Net weight | 1,710 kg |
| Quantity | 5 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 9,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 87.0 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BE-580ED1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 265.44 | not rated | not rated | not rated | not rated | not rated |
| 40 | 432.87 | 264.84 | not rated | not rated | not rated | not rated |
| 45 | 595.26 | 430.65 | 264.33 | not rated | not rated | not rated |
| 50 | 755.99 | 591.58 | 428.78 | 263.99 | not rated | not rated |
| 55 | 915.96 | 750.93 | 588.47 | 427.35 | 263.87 | not rated |
| 60 | 1075.51 | 909.53 | 746.63 | 586.06 | 426.41 | 264.14 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 201.29 | not rated | not rated | not rated | not rated | not rated |
| 40 | 324.68 | 200.74 | not rated | not rated | not rated | not rated |
| 45 | 444.15 | 322.86 | 200.27 | not rated | not rated | not rated |
| 50 | 562.36 | 441.22 | 321.34 | 199.98 | not rated | not rated |
| 55 | 680.00 | 558.38 | 438.77 | 320.20 | 199.92 | not rated |
| 60 | 797.33 | 674.99 | 555.04 | 436.90 | 319.55 | 200.17 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 432.872 | 75.08 | 53.7 |
| Low speed (Y) | 324.675 | 56.31 | 32.1 |
| A | 1808 mm |
|---|---|
| B | 1210 mm |
| C | 6460 mm |
| F | 1050 mm |
| G | 7060 mm |
| E1 | 1230 mm |
| E2 | 1200 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 7060 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.