BE-580ED1-B01 C
432.87 kW
Defrost: None
Product code: BE-2X380AC1-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 120,121 m³/h |
|---|---|
| External surface | 1,728.5 m² |
| Inner volume | 223.5 dm³ |
| Fin material | Aluminium |
| Net weight | 1,799 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BE-2X380AC1-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 255.04 | not rated | not rated | not rated | not rated | not rated |
| 40 | 432.19 | 255.47 | not rated | not rated | not rated | not rated |
| 45 | 604.65 | 431.25 | 255.82 | not rated | not rated | not rated |
| 50 | 775.61 | 602.51 | 430.43 | 256.22 | not rated | not rated |
| 55 | 945.84 | 772.30 | 600.71 | 429.95 | 256.71 | not rated |
| 60 | 1115.67 | 941.40 | 769.52 | 599.41 | 429.75 | 257.39 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 200.30 | not rated | not rated | not rated | not rated | not rated |
| 40 | 335.79 | 200.52 | not rated | not rated | not rated | not rated |
| 45 | 467.39 | 334.88 | 200.73 | not rated | not rated | not rated |
| 50 | 597.66 | 465.47 | 334.13 | 200.99 | not rated | not rated |
| 55 | 727.31 | 594.79 | 463.88 | 333.64 | 201.32 | not rated |
| 60 | 856.62 | 723.51 | 592.40 | 462.74 | 333.51 | 201.89 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 432.188 | 75.00 | 68.1 |
| Low speed (Y) | 335.792 | 58.23 | 43.4 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 4050 mm |
| F | 2230 mm |
| G | 4650 mm |
| E1 | 1250 mm |
| E2 | 1200 mm |
| H | 4300 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 4650 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.