BE-580AD1-B01 C
429.61 kW
Defrost: None
Product code: BE-2X380AC5-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 125,397 m³/h |
|---|---|
| External surface | 1,700.1 m² |
| Inner volume | 259.3 dm³ |
| Fin material | Aluminium |
| Net weight | 1,975 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BE-2X380AC5-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 252.52 | not rated | not rated | not rated | not rated | not rated |
| 40 | 429.79 | 252.90 | not rated | not rated | not rated | not rated |
| 45 | 602.59 | 428.79 | 253.22 | not rated | not rated | not rated |
| 50 | 773.88 | 600.36 | 427.95 | 253.55 | not rated | not rated |
| 55 | 944.55 | 770.45 | 598.39 | 427.32 | 253.99 | not rated |
| 60 | 1114.81 | 939.96 | 767.52 | 596.92 | 427.06 | 254.60 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 200.87 | not rated | not rated | not rated | not rated | not rated |
| 40 | 338.66 | 201.10 | not rated | not rated | not rated | not rated |
| 45 | 472.65 | 337.74 | 201.32 | not rated | not rated | not rated |
| 50 | 605.35 | 470.69 | 336.96 | 201.51 | not rated | not rated |
| 55 | 737.46 | 602.42 | 469.04 | 336.34 | 201.79 | not rated |
| 60 | 869.25 | 733.59 | 599.96 | 467.72 | 336.02 | 202.24 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 429.786 | 74.59 | 53.7 |
| Low speed (Y) | 338.656 | 58.73 | 35.0 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 4050 mm |
| F | 2330 mm |
| G | 4650 mm |
| E1 | 1250 mm |
| E2 | 1200 mm |
| H | 4300 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 4650 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.