Skip to Content

Dry cooler BE-2X380AC5-B01T C

Dry cooler BE-2X380AC5-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2X380AC5-B01T C

Heat rejection i
429.79 kW
Air flow
125,397 m³/h
Fans
6 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 125,397 m³/h
External surface 1,700.1 m²
Inner volume 259.3 dm³
Fin materialAluminium
Net weight 1,975 kg
Fans
Quantity 6
Diameter 800 mm
Speed 900 rpm
Power 10,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 88.0 dB(A)
Energy class D
Connections
Inlet 3"
Outlet 3"
Defrost
BE-2X380AC5-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
429.786 kW Fluid flow 74.59 m³/h Pressure drop 53.7 kPa
Heat rejection · Low speed (Y)
338.656 kW Fluid flow 58.73 m³/h Pressure drop 35.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 252.52 not rated not rated not rated not rated not rated
40 429.79 252.90 not rated not rated not rated not rated
45 602.59 428.79 253.22 not rated not rated not rated
50 773.88 600.36 427.95 253.55 not rated not rated
55 944.55 770.45 598.39 427.32 253.99 not rated
60 1114.81 939.96 767.52 596.92 427.06 254.60

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 200.87 not rated not rated not rated not rated not rated
40 338.66 201.10 not rated not rated not rated not rated
45 472.65 337.74 201.32 not rated not rated not rated
50 605.35 470.69 336.96 201.51 not rated not rated
55 737.46 602.42 469.04 336.34 201.79 not rated
60 869.25 733.59 599.96 467.72 336.02 202.24

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 429.786 74.59 53.7
Low speed (Y) 338.656 58.73 35.0

Dimensions

Dimension drawing of BE-2X380AC5-B01T C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 2400 mm
C 4050 mm
F 2330 mm
G 4650 mm
E1 1250 mm
E2 1200 mm
H 4300 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 4650 mm
Width 2400 mm
Height 2750 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.