BE-2X380AC5-B01T C
429.79 kW
Defrost: None
Product code: BE-580AD1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 103,001 m³/h |
|---|---|
| External surface | 2,352.8 m² |
| Inner volume | 276.2 dm³ |
| Fin material | Aluminium |
| Net weight | 1,634 kg |
| Quantity | 5 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 9,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 87.0 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BE-580AD1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 261.09 | not rated | not rated | not rated | not rated | not rated |
| 40 | 429.61 | 260.61 | not rated | not rated | not rated | not rated |
| 45 | 593.16 | 427.46 | 260.16 | not rated | not rated | not rated |
| 50 | 755.06 | 589.53 | 425.62 | 259.88 | not rated | not rated |
| 55 | 916.19 | 750.00 | 586.41 | 424.20 | 259.81 | not rated |
| 60 | 1076.91 | 909.74 | 745.66 | 583.95 | 423.30 | 260.07 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 201.09 | not rated | not rated | not rated | not rated | not rated |
| 40 | 327.22 | 200.64 | not rated | not rated | not rated | not rated |
| 45 | 449.35 | 325.46 | 200.25 | not rated | not rated | not rated |
| 50 | 570.19 | 446.45 | 323.98 | 199.99 | not rated | not rated |
| 55 | 690.42 | 566.20 | 444.00 | 322.84 | 199.95 | not rated |
| 60 | 810.34 | 685.38 | 562.82 | 442.09 | 322.17 | 200.19 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 429.606 | 74.50 | 67.8 |
| Low speed (Y) | 327.218 | 56.76 | 41.8 |
| A | 1808 mm |
|---|---|
| B | 1210 mm |
| C | 6460 mm |
| F | 1050 mm |
| G | 7060 mm |
| E1 | 1230 mm |
| E2 | 1200 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 7060 mm |
|---|---|
| Width | 1210 mm |
| Height | 1808 mm |
Our engineers answer with a selection for your conditions.