BE-580AD1-B01 C
429.61 kW
Defrost: None
Product code: BE-2x380BD1-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 114,016 m³/h |
|---|---|
| External surface | 1,499.3 m² |
| Inner volume | 191.7 dm³ |
| Fin material | Aluminium |
| Net weight | 1,716 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.1 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BE-2x380BD1-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 256.93 | not rated | not rated | not rated | not rated | not rated |
| 40 | 429.00 | 257.15 | not rated | not rated | not rated | not rated |
| 45 | 596.60 | 428.05 | 257.37 | not rated | not rated | not rated |
| 50 | 762.71 | 594.59 | 427.30 | 257.62 | not rated | not rated |
| 55 | 928.12 | 759.69 | 593.00 | 426.75 | 258.03 | not rated |
| 60 | 1093.16 | 924.15 | 757.28 | 591.75 | 426.65 | 258.71 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 198.25 | not rated | not rated | not rated | not rated | not rated |
| 40 | 327.86 | 198.22 | not rated | not rated | not rated | not rated |
| 45 | 453.79 | 326.85 | 198.25 | not rated | not rated | not rated |
| 50 | 578.50 | 451.88 | 326.04 | 198.40 | not rated | not rated |
| 55 | 702.65 | 575.74 | 450.34 | 325.53 | 198.69 | not rated |
| 60 | 826.49 | 699.06 | 573.49 | 449.26 | 325.41 | 199.24 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 429.002 | 74.40 | 105.5 |
| Low speed (Y) | 327.858 | 56.86 | 65.5 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 3750 mm |
| F | 2230 mm |
| G | 4350 mm |
| E1 | 1150 mm |
| E2 | 1100 mm |
| H | 4000 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 4350 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.