BE-2x291CB1-B04T C
428.16 kW
Defrost: None
Product code: BE-2X380BC1-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 123,144 m³/h |
|---|---|
| External surface | 1,421.1 m² |
| Inner volume | 191.9 dm³ |
| Fin material | Aluminium |
| Net weight | 1,834 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BE-2X380BC1-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 254.21 | not rated | not rated | not rated | not rated | not rated |
| 40 | 428.17 | 254.29 | not rated | not rated | not rated | not rated |
| 45 | 597.94 | 427.02 | 254.39 | not rated | not rated | not rated |
| 50 | 766.25 | 595.61 | 426.02 | 254.52 | not rated | not rated |
| 55 | 933.98 | 762.83 | 593.60 | 425.30 | 254.79 | not rated |
| 60 | 1101.36 | 929.47 | 759.91 | 592.10 | 424.93 | 255.30 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 199.63 | not rated | not rated | not rated | not rated | not rated |
| 40 | 333.38 | 199.67 | not rated | not rated | not rated | not rated |
| 45 | 463.64 | 332.38 | 199.70 | not rated | not rated | not rated |
| 50 | 592.73 | 461.71 | 331.55 | 199.81 | not rated | not rated |
| 55 | 721.29 | 589.92 | 460.10 | 330.97 | 200.04 | not rated |
| 60 | 849.55 | 717.61 | 587.58 | 458.92 | 330.74 | 200.47 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 428.171 | 74.31 | 114.8 |
| Low speed (Y) | 333.379 | 57.81 | 73.5 |
| A | 2778 mm |
|---|---|
| B | 2400 mm |
| C | 3750 mm |
| F | 2330 mm |
| G | 4350 mm |
| E1 | 1150 mm |
| E2 | 1100 mm |
| H | 4000 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 4350 mm |
|---|---|
| Width | 2400 mm |
| Height | 2778 mm |
Our engineers answer with a selection for your conditions.