Skip to Content

Dry cooler BE-2x291CB1-B04T C

Dry cooler BE-2x291CB1-B04T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x291CB1-B04T C

Heat rejection i
428.16 kW
Air flow
119,475 m³/h
Fans
4 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 119,475 m³/h
External surface 2,010.9 m²
Inner volume 259.3 dm³
Fin materialAluminium
Net weight 1,893 kg
Fans
Quantity 4
Diameter 910 mm
Speed 840 rpm
Power 11,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 63.0 dB(A)
Sound power 96.0 dB(A)
Energy class D
Connections
Inlet 3"
Outlet 3"
Defrost
BE-2x291CB1-B04T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
428.161 kW Fluid flow 74.30 m³/h Pressure drop 106.1 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
342.065 kW Fluid flow 59.33 m³/h Pressure drop 71.2 kPa above the recommended pressure drop

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 255.32 not rated not rated not rated not rated not rated
40 428.16 254.97 not rated not rated not rated not rated
45 596.77 426.35 254.64 not rated not rated not rated
50 764.05 593.59 424.75 254.41 not rated not rated
55 930.70 759.54 590.79 423.36 254.30 not rated
60 1096.97 924.86 755.55 588.46 422.46 254.44

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 205.73 not rated not rated not rated not rated not rated
40 342.07 205.33 not rated not rated not rated not rated
45 474.86 340.37 204.92 not rated not rated not rated
50 606.49 472.00 338.87 204.63 not rated not rated
55 737.57 602.48 469.46 337.63 204.41 not rated
60 868.34 732.43 598.93 467.36 336.75 204.46

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 428.161 74.30 106.1
Low speed (Y) 342.065 59.33 71.2

Dimensions

Dimension drawing of BE-2x291CB1-B04T C
Dimension drawing
Dimensions as drawn
A 2880 mm
B 2400 mm
C 5250 mm
F 2330 mm
G 5850 mm
E1 2450 mm
H 5500 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 5850 mm
Width 2400 mm
Height 2880 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.