Skip to Content

Dry cooler BE-880AC5-B01 C

Dry cooler BE-880AC5-B01 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-880AC5-B01 C

Heat rejection i
607.09 kW
Air flow
170,245 m³/h
Fans
8 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 170,245 m³/h
External surface 2,547.0 m²
Inner volume 369.8 dm³
Fin materialAluminium
Net weight 2,299 kg
Fans
Quantity 8
Diameter 800 mm
Speed 900 rpm
Power 14,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 89.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BE-880AC5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
607.094 kW Fluid flow 105.36 m³/h Pressure drop 88.3 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
476.983 kW Fluid flow 82.73 m³/h Pressure drop 57.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 361.80 not rated not rated not rated not rated not rated
40 607.09 361.56 not rated not rated not rated not rated
45 846.36 604.89 361.29 not rated not rated not rated
50 1083.72 842.34 602.94 361.13 not rated not rated
55 1320.20 1077.96 838.82 601.35 361.22 not rated
60 1556.15 1312.70 1072.94 836.03 600.37 361.60

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 286.96 not rated not rated not rated not rated not rated
40 476.98 286.62 not rated not rated not rated not rated
45 662.03 474.98 286.28 not rated not rated not rated
50 845.45 658.56 473.27 286.10 not rated not rated
55 1028.08 840.51 655.54 471.93 286.04 not rated
60 1210.29 1021.72 836.25 653.15 471.09 286.34

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 607.094 105.36 88.3
Low speed (Y) 476.983 82.73 57.5

Dimensions

Dimension drawing of BE-880AC5-B01 C
Dimension drawing
Dimensions as drawn
A 1808 mm
B 1150 mm
C 10060 mm
F 1050 mm
G 10660 mm
E1 1230 mm
E2 1200 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 10660 mm
Width 1300 mm
Height 1808 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.