Skip to Content

Dry cooler BE-880EB1-B01 C

Dry cooler BE-880EB1-B01 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-880EB1-B01 C

Heat rejection i
592.74 kW
Air flow
169,576 m³/h
Fans
8 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 169,576 m³/h
External surface 2,144.5 m²
Inner volume 424.5 dm³
Fin materialAluminium
Net weight 2,237 kg
Fans
Quantity 8
Diameter 800 mm
Speed 900 rpm
Power 14,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 89.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BE-880EB1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
592.739 kW Fluid flow 102.86 m³/h Pressure drop 50.2 kPa
Heat rejection · Low speed (Y)
464.754 kW Fluid flow 80.60 m³/h Pressure drop 32.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 349.46 not rated not rated not rated not rated not rated
40 592.74 349.74 not rated not rated not rated not rated
45 829.99 591.12 349.96 not rated not rated not rated
50 1065.13 826.50 589.67 350.21 not rated not rated
55 1299.39 1060.01 823.56 588.54 350.59 not rated
60 1533.16 1292.64 1055.60 821.14 587.82 351.28

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 276.54 not rated not rated not rated not rated not rated
40 464.75 276.62 not rated not rated not rated not rated
45 647.86 463.18 276.66 not rated not rated not rated
50 829.24 644.78 461.80 276.77 not rated not rated
55 1009.83 824.76 642.16 460.78 277.04 not rated
60 1189.97 1003.96 820.90 640.09 460.21 277.57

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 592.739 102.86 50.2
Low speed (Y) 464.754 80.60 32.6

Dimensions

Dimension drawing of BE-880EB1-B01 C
Dimension drawing
Dimensions as drawn
A 1808 mm
B 1300 mm
C 10060 mm
F 1150 mm
G 10660 mm
E1 1230 mm
E2 1200 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 10660 mm
Width 1300 mm
Height 1808 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.