Dry cooler BE-2x491BC5-C04C C

Dry cooler BE-2x491BC5-C04C C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-2x491BC5-C04C C

Heat rejection i
592.28 kW
Air flow
209,979 m³/h
Fans
8 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 209,979 m³/h
External surface 1,432.4 m²
Inner volume 241.5 dm³
Fin materialAluminium
Net weight 2,157 kg
Fans
Quantity 8
Diameter 910 mm
Speed 840 rpm
Power 22,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 67.0 dB(A)
Sound power 99.4 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BE-2x491BC5-C04C C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
592.275 kW Fluid flow 102.80 m³/h Pressure drop 60.8 kPa
Heat rejection · Low speed (Y)
471.351 kW Fluid flow 81.80 m³/h Pressure drop 40.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 341.35 not rated not rated not rated not rated not rated
40 592.28 342.85 not rated not rated not rated not rated
45 837.68 592.35 344.17 not rated not rated not rated
50 1081.30 836.52 592.49 345.36 not rated not rated
55 1324.15 1078.98 835.64 592.81 346.63 not rated
60 1566.52 1320.70 1077.16 835.17 593.46 348.07

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 273.53 not rated not rated not rated not rated not rated
40 471.35 274.81 not rated not rated not rated not rated
45 664.26 471.42 275.91 not rated not rated not rated
50 855.55 663.31 471.56 276.97 not rated not rated
55 1046.16 853.71 662.64 471.89 278.08 not rated
60 1236.34 1043.39 852.27 662.37 472.55 279.37

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 592.275 102.80 60.8
Low speed (Y) 471.351 81.80 40.5

Dimensions

Dimension drawing of BE-2x491BC5-C04C C
Dimension drawing
Dimensions as drawn
A 2511 mm
B 2300 mm
C 5250 mm
F 2230 mm
G 5850 mm
E1 1230 mm
E2 2400 mm
H 5500 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 5250 mm
Width 2300 mm
Height 2511 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.