BE-2x480AD5-B01C C
590.80 kW
Defrost: None
Product code: BE-t-2x391GC5-B04T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 160,259 m³/h |
|---|---|
| External surface | 1,313.0 m² |
| Inner volume | 242.6 dm³ |
| Fin material | Aluminium |
| Net weight | 1,895 kg |
| Quantity | 6 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 16,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 66.0 dB(A) |
|---|---|
| Sound power | 98.1 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-t-2x391GC5-B04T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 350.24 | not rated | not rated | not rated | not rated | not rated |
| 40 | 591.03 | 350.60 | not rated | not rated | not rated | not rated |
| 45 | 825.27 | 589.37 | 350.92 | not rated | not rated | not rated |
| 50 | 1057.40 | 821.94 | 588.05 | 351.33 | not rated | not rated |
| 55 | 1288.53 | 1052.40 | 819.13 | 587.14 | 351.92 | not rated |
| 60 | 1519.09 | 1281.90 | 1048.20 | 817.04 | 586.79 | 352.81 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 276.06 | not rated | not rated | not rated | not rated | not rated |
| 40 | 460.98 | 276.31 | not rated | not rated | not rated | not rated |
| 45 | 640.41 | 459.65 | 276.55 | not rated | not rated | not rated |
| 50 | 818.01 | 637.70 | 458.56 | 276.80 | not rated | not rated |
| 55 | 994.75 | 814.00 | 635.47 | 457.85 | 277.32 | not rated |
| 60 | 1171.01 | 989.47 | 810.68 | 633.88 | 457.66 | 278.12 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 591.028 | 102.57 | 80.4 |
| Low speed (Y) | 460.978 | 79.95 | 51.7 |
| A | 2910 mm |
|---|---|
| B | 2400 mm |
| C | 4050 mm |
| F | 2330 mm |
| G | 4650 mm |
| E1 | 1250 mm |
| E2 | 1200 mm |
| H | 4300 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 4650 mm |
|---|---|
| Width | 2400 mm |
| Height | 2910 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.