BE-t-2x391GC5-B04T C
591.03 kW
Defrost: None
Product code: BE-2x480AD5-B01C C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 157,377 m³/h |
|---|---|
| External surface | 2,435.5 m² |
| Inner volume | 374.1 dm³ |
| Fin material | Aluminium |
| Net weight | 2,403 kg |
| Quantity | 8 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 14,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 89.0 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BE-2x480AD5-B01C C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 354.18 | not rated | not rated | not rated | not rated | not rated |
| 40 | 590.80 | 354.13 | not rated | not rated | not rated | not rated |
| 45 | 821.44 | 589.00 | 354.08 | not rated | not rated | not rated |
| 50 | 1050.08 | 818.04 | 587.50 | 354.21 | not rated | not rated |
| 55 | 1277.80 | 1045.14 | 815.23 | 586.46 | 354.57 | not rated |
| 60 | 1505.00 | 1271.36 | 1041.04 | 813.15 | 586.06 | 355.31 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 275.97 | not rated | not rated | not rated | not rated | not rated |
| 40 | 455.47 | 275.69 | not rated | not rated | not rated | not rated |
| 45 | 630.03 | 453.80 | 275.56 | not rated | not rated | not rated |
| 50 | 802.94 | 627.06 | 452.46 | 275.58 | not rated | not rated |
| 55 | 975.09 | 798.72 | 624.63 | 451.54 | 275.82 | not rated |
| 60 | 1146.82 | 969.64 | 795.25 | 622.88 | 451.16 | 276.42 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 590.799 | 102.47 | 96.7 |
| Low speed (Y) | 455.466 | 78.99 | 61.0 |
| A | 2453 mm |
|---|---|
| B | 2300 mm |
| C | 5250 mm |
| F | 2230 mm |
| G | 5850 mm |
| E1 | 1250 mm |
| E2 | 2400 mm |
| H | 5500 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 5850 mm |
|---|---|
| Width | 2300 mm |
| Height | 2453 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.