Skip to Content

Dry cooler BE-t-280HB1-B01 C

Dry cooler BE-t-280HB1-B01 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-t-280HB1-B01 C

Heat rejection i
184.63 kW
Air flow
44,282 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 44,282 m³/h
External surface 634.1 m²
Inner volume 75.2 dm³
Fin materialAluminium
Net weight 679 kg
Fans
Quantity 2
Diameter 800 mm
Speed 900 rpm
Power 3,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 51.0 dB(A)
Sound power 83.0 dB(A)
Energy class D
Connections
Inlet 2"
Outlet 2"
Defrost
BE-t-280HB1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
184.633 kW Fluid flow 32.02 m³/h Pressure drop 112.6 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
142.456 kW Fluid flow 24.71 m³/h Pressure drop 71.1 kPa above the recommended pressure drop

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 112.51 not rated not rated not rated not rated not rated
40 184.63 112.15 not rated not rated not rated not rated
45 254.69 183.49 111.80 not rated not rated not rated
50 324.06 252.84 182.48 111.53 not rated not rated
55 393.12 321.53 251.21 181.65 111.35 not rated
60 462.01 389.92 319.31 249.87 181.04 111.32

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 87.70 not rated not rated not rated not rated not rated
40 142.46 87.35 not rated not rated not rated not rated
45 195.55 141.48 87.03 not rated not rated not rated
50 248.10 194.00 140.61 86.77 not rated not rated
55 300.41 246.01 192.64 139.90 86.61 not rated
60 352.57 297.78 244.18 191.52 139.39 86.56

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 184.633 32.02 112.6
Low speed (Y) 142.456 24.71 71.1

Dimensions

Dimension drawing of BE-t-280HB1-B01 C
Dimension drawing
Dimensions as drawn
A 1808 mm
B 1210 mm
C 4060 mm
F 1050 mm
G 4660 mm
E1 1830 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 4660 mm
Width 1210 mm
Height 1808 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.