Skip to Content

Dry cooler BE-t-2x180HC5-B01T C

Dry cooler BE-t-2x180HC5-B01T C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-t-2x180HC5-B01T C

Heat rejection i
185.83 kW
Air flow
43,581 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 43,581 m³/h
External surface 656.2 m²
Inner volume 97.3 dm³
Fin materialAluminium
Net weight 964 kg
Fans
Quantity 2
Diameter 800 mm
Speed 900 rpm
Power 3,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 51.0 dB(A)
Sound power 83.0 dB(A)
Energy class D
Connections
Inlet 2"
Outlet 2"
Defrost
BE-t-2x180HC5-B01T C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
185.827 kW Fluid flow 32.23 m³/h Pressure drop 47.1 kPa
Heat rejection · Low speed (Y)
142.308 kW Fluid flow 24.68 m³/h Pressure drop 29.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 112.78 not rated not rated not rated not rated not rated
40 185.83 112.56 not rated not rated not rated not rated
45 256.44 184.74 112.34 not rated not rated not rated
50 326.25 254.59 183.77 112.17 not rated not rated
55 395.70 323.68 252.97 182.98 112.09 not rated
60 464.94 392.43 321.44 251.64 182.43 112.16

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 87.26 not rated not rated not rated not rated not rated
40 142.31 87.04 not rated not rated not rated not rated
45 195.37 141.38 86.84 not rated not rated not rated
50 247.79 193.84 140.57 86.68 not rated not rated
55 299.93 245.70 192.51 139.91 86.59 not rated
60 351.91 297.29 243.89 191.42 139.44 86.58

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 185.827 32.23 47.1
Low speed (Y) 142.308 24.68 29.2

Dimensions

Dimension drawing of BE-t-2x180HC5-B01T C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 2400 mm
C 2250 mm
F 2330 mm
G 2850 mm
E1 1850 mm
H 2500 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 2850 mm
Width 2400 mm
Height 2750 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.