BE-291DB1-B04 C
185.74 kW
Defrost: None
Product code: BE-t-2x180HC5-B01T C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 43,581 m³/h |
|---|---|
| External surface | 656.2 m² |
| Inner volume | 97.3 dm³ |
| Fin material | Aluminium |
| Net weight | 964 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 3,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | D |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BE-t-2x180HC5-B01T C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 112.78 | not rated | not rated | not rated | not rated | not rated |
| 40 | 185.83 | 112.56 | not rated | not rated | not rated | not rated |
| 45 | 256.44 | 184.74 | 112.34 | not rated | not rated | not rated |
| 50 | 326.25 | 254.59 | 183.77 | 112.17 | not rated | not rated |
| 55 | 395.70 | 323.68 | 252.97 | 182.98 | 112.09 | not rated |
| 60 | 464.94 | 392.43 | 321.44 | 251.64 | 182.43 | 112.16 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 87.26 | not rated | not rated | not rated | not rated | not rated |
| 40 | 142.31 | 87.04 | not rated | not rated | not rated | not rated |
| 45 | 195.37 | 141.38 | 86.84 | not rated | not rated | not rated |
| 50 | 247.79 | 193.84 | 140.57 | 86.68 | not rated | not rated |
| 55 | 299.93 | 245.70 | 192.51 | 139.91 | 86.59 | not rated |
| 60 | 351.91 | 297.29 | 243.89 | 191.42 | 139.44 | 86.58 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 185.827 | 32.23 | 47.1 |
| Low speed (Y) | 142.308 | 24.68 | 29.2 |
| A | 2750 mm |
|---|---|
| B | 2400 mm |
| C | 2250 mm |
| F | 2330 mm |
| G | 2850 mm |
| E1 | 1850 mm |
| H | 2500 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 2850 mm |
|---|---|
| Width | 2400 mm |
| Height | 2750 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.