Skip to Content

Dry cooler BE-t-291GB5-B04 C

Dry cooler BE-t-291GB5-B04 C
Illustrative photo

Producer: Karyer · Line: BE (Dry)

Product code: BE-t-291GB5-B04 C

Heat rejection i
176.97 kW
Air flow
55,952 m³/h
Fans
2 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BE — BE = V-type dry cooler.
  • B
    Fin type (optional "t"): t — t: louvered fins (high-efficiency fin surface)
  • D
    Number of fans per row: 2 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 91 — Ø910 mm
  • G
    Coil tube rows (2nd dimensional letter): B — 3 tube rows
  • H
    Fin spacing: 5 — 2.5 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 04 — three-phase 400 V 50 Hz, 6-pole AC fan (in this series)

Data

Coil
Air flow 55,952 m³/h
External surface 358.1 m²
Inner volume 55.0 dm³
Fin materialAluminium
Net weight 557 kg
Fans
Quantity 2
Diameter 910 mm
Speed 840 rpm
Power 5,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 61.0 dB(A)
Sound power 93.0 dB(A)
Energy class E
Connections
Inlet 2"
Outlet 2"
Defrost
BE-t-291GB5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
176.965 kW Fluid flow 30.72 m³/h Pressure drop 74.3 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
142.381 kW Fluid flow 24.71 m³/h Pressure drop 50.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 102.78 not rated not rated not rated not rated not rated
40 176.97 103.05 not rated not rated not rated not rated
45 249.39 176.70 103.29 not rated not rated not rated
50 321.25 248.64 176.48 103.52 not rated not rated
55 392.83 320.03 248.01 176.34 103.77 not rated
60 464.27 391.17 319.00 247.54 176.33 104.09

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 83.37 not rated not rated not rated not rated not rated
40 142.38 83.58 not rated not rated not rated not rated
45 199.82 142.10 83.74 not rated not rated not rated
50 256.72 199.13 141.87 83.91 not rated not rated
55 313.41 255.64 198.52 141.72 84.10 not rated
60 369.96 311.94 254.71 198.08 141.68 84.35

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 176.965 30.72 74.3
Low speed (Y) 142.381 24.71 50.5

Dimensions

Dimension drawing of BE-t-291GB5-B04 C
Dimension drawing
Dimensions as drawn
A 1958 mm
B 1210 mm
C 2860 mm
F 1050 mm
G 3460 mm
E1 1230 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 3460 mm
Width 1210 mm
Height 1958 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.